background image

10

V - CHECKOUT PROCEDURES AND ADjUSTMENTS

Drill a ½” hole in the plastic CPVC vent pipe or exhaust 

2. 

tee, just large enough to allow access for the sample 

probe of your combustion analyzer.
Turn the thermostat to the closed position so the appli

-

3. 

ance is activated.

Set appliance to high fire mode as described in the 

4. 

“User Interface Quick Reference” section of this manual 

and allow it to run for approximately 5 minutes.
Insert the sample probe of your combustion analyzer 

5. 

into the hole you drilled in Step 2 about halfway into 

the exhaust gas stream. Take a flue gas reading and 

observe the % CO2 and CO values.  Adjust the throttle 

screw until the correct readings are reached. turning 
the throttle screw clockwise decreases the rate and the 
Co2 value. turning the throttle screw counter clockwise 
increases the rate and the Co2 value. allow the ap-

pliance to stabilize for approximately one minute after 

adjusting the throttle screw before you take a reading 

with your combustion analyzer.

IMPORTANT: Under all conditions CO levels 

should not exceed 80 ppm.

Set appliance to low fire mode as described in the “User 

6. 

Interface Quick Reference” section of this manual and 

check CO2 level as stated in Step 5. Low fire and high 

fire values should be approximately the same.
After adjustments are made stop the appliance, dis

-

7. 

connect the pressure gauge, tighten the inlet pressure 

tap on the gas valve, remove the CO2 meter from the 

CPVC pipe, and seal the hole with a ¼” NPT black iron 

plug. Use thread sealing compound or teflon tape to 

ensure a proper seal.

Return the thermostat switch to its original position.

8. 

Installers:  Complete  and  sign  the  “Installa-

tion and Checkout Certificate” on the last page 

of this manual.

MEASURE THE NATURAL GAS INPUT RATE

Correct input rate is essential for proper and efficient 

operation of the burner and boiler.

Determine the elevation at the installation site.

1. 

See Table 2 in Section IV of the separate “Installation 

2. 

Manual” (P/N# 240006103) to determine the correct ap

-

proximate input rate for the local elevation.
Obtain the yearly average heating value of the local gas 

3. 

utility. At sea level elevation, it should be approximately 

1000 BTU per standard cubic foot.

Operate boiler for 5 minutes.

4. 

Turn off all other gas appliances, extinguishing standing 

5. 

pilots where applicable.
At the gas meter, measure the time in seconds required 

6. 

to use one cubic foot of gas.

NOTE:

 

Boiler must be in high fire mode for this operation. 

See the “User Interface Quick Reference” in this manual for 

more information on putting the boiler in high fire mode.

Calculate the BTUH Input Rate as follows:

7. 

Btuh input rate =

3600 x heating value from Step 3

16 +/- 2 seconds

The measured input rate will vary with vent length, gas 

8. 

calorific content, altitude and ambient temperature. The 

boiler should be set up with the combustion specifica

-

tions in the “Boiler Adjustment” section.

DETERMINE LP GAS INPUT RATE

LP gas input rate is determined by measuring the C0

2

 

produced  during  combustion.  This  value  should  be 

set according to the guidelines table on the following 

page.

MEASURE FLAME SENSE

Flame sense can be an indicator of issues with air in

-

take venting, exhaust venting, burner and ignitor con

-

dition and supply gas piping pressure. Using a multim

-

eter capable of reading 0-20 VDC, attach one lead to 

the “F” terminal on the low voltage terminal block on 

the boiler control, and the other to any ground surface 

on the boiler. See Figure #2. The flame sense voltage 

must  be  in  accordance  with  the  values  listed  in  the 

Flame Signal Guidelines chart later in this manual.

Figure #2

Summary of Contents for 95M-200

Page 1: ...instructions including the Installation Manual P N 240006103 the Parameter Guide P N 240006105 the User s Information Manual P N 240006106 and this Control Manual and Oper ating Instructions before attempting to program the control and be sure to perform all steps in the order specified Failure to comply could re sult in severe personal injury death or substan tial property damage Revise boiler co...

Page 2: ...2 ...

Page 3: ...ntial property damage DANGER Indicates a potentially hazardous situation which if not avoided could result in death serious in jury or substantial property damage WARNING Indicates a potential hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices CAUTION IMPORTANT Read the following instructions completely before insta...

Page 4: ...rature is too high the control shuts the boiler down This ensures boiler shut down in the event of low water or low flow conditions Some codes and jurisdictions may accept these integral 2 features of the control in lieu of requiring an additional limit control or low water cutoff Consult your local jurisdiction for more information on low water cutoff requirements This boiler is controlled by a m...

Page 5: ...used Target temperature with outdoor reset All boilers are shipped with an outdoor temperature sensor When this sen sor is installed low voltage terminal strip terminals A1 and A2 the boiler control regulates target outlet water temper ature based on outside temperature Set the temperature curve by setting Parameter 4 to ODT outdoor design temperature for the area For ODT of 0 F or lower set Param...

Page 6: ...grammed into the con troller Display user interface By means of the display user interface the installer and home owner can scroll through the control settings and customize the boiler to the heat delivery system used in the location of installation See the User Interface Quick Reference in Section X of this manual for more information on using and programming the boiler control immediately sets t...

Page 7: ...eed will increase to igni tion speed The blower will run in prepurge for 10 sec onds 2180 Ignition After prepurge the control module opens the gas valve and starts ignition spark If burner flame proves within 4 5 seconds burner con tinues to fire Burner will fire at startup rate for about 10 seconds to allow flame to stabilize If burner flame does not prove within 4 5 seconds con trol module attem...

Page 8: ...re 6150 Target temperature reached The burner will shut down The blower will run in postpurge see be low then turn off DHW circulator continues to run as long as there is a call for DHW heating Lower DHW aquastat to stop call for heat 6 1150 Postpurge When room thermostat is satisfied call for heat ended burner turns off Blower will con tinue for 15 second postpurge then turn off If another DHW he...

Page 9: ...s 100 F Test Low Water Cut Off Disconnect the wire from the LWCO sensor probe 1 Set thermostat for call for heat 2 Boiler should not begin normal sequence of operation 3 Attach wire to the sensor probe 4 Return thermostat to previous setting 5 Test other field installed safety con trols if used If the boiler is equipped with any additional safety controls test for operation as outlined by the cont...

Page 10: ...ast page of this manual Measure the natural gas input rate Correct input rate is essential for proper and efficient operation of the burner and boiler Determine the elevation at the installation site 1 See Table 2 in Section IV of the separate Installation 2 Manual P N 240006103 to determine the correct ap proximate input rate for the local elevation Obtain the yearly average heating value of the ...

Page 11: ...ngth and altitude of installation Combustion Guidelines Outside Natural Gas LP Gas Temperature CO2 O2 CO CO2 O2 CO 70 F and up 9 6 to 10 3 9 to 3 2 Less than 80 PPM 11 1 to 11 5 4 1 to 3 4 Less than 80 PPM 21 C and up 30 F to 70 F 9 3 to 9 6 4 4 to 3 9 Less than 80 PPM 10 8 to 11 1 4 5 to 4 1 Less than 80 PPM 1 C to 21 C 30 F and below 9 0 to 9 3 5 0 to 4 4 Less than 80 PPM 10 5 to 10 8 4 9 to 4 5...

Page 12: ...12 VI Detailed Sequence of Operation ...

Page 13: ...ntinuity Tester Contact Thermometer Inclined Manometer or Pressure Gauge with 0 6 0 range 0 01 scale for measuring suction pressures at pres sure switch U Tube Manometer or Differential Pressure Gauge with 0 14 range 0 1 scale for measuring inlet and manifold gas pressures INITIAL SERVICE CHECKS Prior to troubleshooting Make sure that circuit breaker is on or fuse is okay at 1 electrical panel Mak...

Page 14: ...t exchanger or vent blockage To check the differential air pressure Turn off service switch or lower thermostat setting 1 Remove vinyl caps from tee 2 Install testing lines as shown to inclined manometer or 3 differential pressure gauge with the ability to read 0 01 increments to at least 6 0 w c Turn on service switch and set thermostat to call for 4 heat Boiler Status Diff Pressure Switch Contac...

Page 15: ...nal line switch and verify 8 boiler operation after completing boiler service Checking temperature sensors The boiler temperature sensors outdoor return water and 1 supply water are all resistance type devices The table below shows the correct resistance value for 2 the sensor at various temperatures Temp F Sensor Ohms Temp F Sensor Ohms Min Max Min Max 32 34 265 37 871 130 3 698 4 088 40 27 834 3...

Page 16: ... mode Display flashes 9 then b Last two digits show code number 1 See User Interface Quick Reference and Soft Lockout Troubleshooting in this manual for for more information on the soft lockout code SOFT LOCKOUT Display flashes 9 and then b in first position last two digits on steady code Code Reason For Soft Lockout Corrective Actions pressing RESET should restart boiler immediately WARNING Elect...

Page 17: ... wait for temperature to drop below 180 degrees 2 Check water level in boiler fill if low Press LWCO reset switch on display panel If problem still exists check LWCO probe and board according to manufacturer s instructions Replace if necessary 3 Check pressure switch for proper operation Replace if moisture has entered switch Check venting for blockage Clear if present 29 Blower turning when it sh...

Page 18: ... lines of air if necessary Verify flue gas vent and air supply piping are correctly installed in good condition and free of obstructions Check voltage to gas valve it should be approx 19 21 vdc 24 vrac during ignition attempt Check gas meter to verify gas flows when gas valve is activated Remove and inspect clean ignition electrode Clean white oxides if necessary and replace ignition electrode if ...

Page 19: ...e problem 28 Blower not running 1 Turn off power to boiler Remove line voltage connector at blower Restart boiler and check voltage across blower plug terminals If 120 vac is NOT present inspect wiring and tightness of connections Replace line voltage wire harness if necessary Replace control module if wire harness replacement doesn t resolve 2 If 120 vac is present on blower wire harness replace ...

Page 20: ...e first character shows boiler status followed by boiler outlet water temp If the burner is being held off due to a soft lockout the display alternates between showing 9 followed by boiler outlet water temp and b followed by the two digit codes below Soft lockout means the boiler will start again automatically if the condition is corrected or timed out Press RESET button to restart boiler without ...

Page 21: ...ys 1 After the STORE button is pressed the set value will flash twice to confirm the change Change will take effect after you leave Parameter Mode IX user interface quick reference INFORMATION MODE Press MODE button 2 times from Standby Mode Display shows Info until a key is pressed Info then displays Parameter Flashing Dot and Current Status 1 190 Press and Hold Key s in BLACK 1 Duration Result D...

Page 22: ...ries 19 Return water temperature higher than 190 F 03 Gas valve disconnected 25 Outlet temperature increased too fast 04 Power lost after lockout 28 No signal from blower blower not running or defective blower motor 05 Internal control failure 29 Blower signal not 0 when it should be 06 Internal control failure 30 Max difference b30 was too large for 20 successive times Non adjustable default max ...

Page 23: ......

Page 24: ...echnical assistance with this product in the United States call toll free 1 800 325 5479 and in Canada call toll free 1 888 270 8324 ECR International PO Box 4729 Utica NY 13504 4729 www ecrinternational com ...

Reviews: