background image

5

GENERAL INSTRUCTIONS

Before seasonal start up it is advisable to have qualified 

service agency check boiler for soot and scale in the flues, 

clean burners and check gas input rate to maintain high 

operating efficiency. Service agency should make certain 

system is filled with water to minimum pressure and 

open air vents - if used - to expel any air that may have 

accumulated in system. Entire piping system should also be 

checked and if any leaks appear, they should be repaired 

immediately.

Venting system should also be inspected at start of each 

heating season. Vent pipe from boiler should be checked for 

signs of deterioration or sagging joints. Repair if necessary.

Following procedure should be followed to clean and check 

flue gas passageways:

Remove burners from combustion chamber by raising 

1. 

burners up from manifold orifices and pulling toward 

front of boiler, (See Figure 4)

Disconnect vent pipe from vent adapter.

2. 

Remove jacket front panel. (See Figure 5)

3. 

Check venter assembly suction pressure.

4. 

Connect slope manometer between venter and 

• 

pressure switch with tee and additional tubing and 

connectors.

Turn boiler on and read suction pressure on 

• 

manometer. Reading should be negative (-) .55 

± .05 inches of water column or higher for DV50 

thru 150 and negative (-) .65 ± .05 inches of water 

column or higher for DV200. If this reading is not 
attainable, contact qualified service agency.

Remove flue collector and venter assembly from boiler 

5. 

castings by loosening hold-down bolts located on each 

side of flue collector. (See Figure 3)

Visually inspect venter assembly for any unusual wear 

6. 

or dirt build up.

If venter has oil cups lubricate venter motor once a 

7. 

month during heating season with few drops of non-

detergent motor oil (SAE 20 or 30). Do not over oil.

Place sheet of heavy paper or similar material in 

8. 

bottom of combustion chamber and brush down flue 

passageways. Soot and scale will collect on paper and 
is easily removed with paper.

Visual check of main burner and pilot flames should be 

made at start of heating season and again in mid-season.

Main burner flame should have well defined inner blue 

mantel with lighter blue outer mantel. (See Figure 6) If 

flame does not appear this way, check burner throats and 

burner orifices for lint or dust obstructions.

Pilot flame should envelop 3/8 to 1/2 inch of tip of ignition 

electrode (See Figure 7). To adjust pilot flame, remove pilot 

adjustment cover screw on gas valve and turn inner screw 
clockwise 

 to decrease or counterclockwise 

 to 

increase pilot flame. See Figure 1. Be sure to replace cover 

screw after adjustment to prevent possible gas leakage.

Burners and pilot should be checked for signs of corrosion, 

rust or scale build-up, and cleaned with nylon bristle brush.

Area around boiler must be kept clear and free of 

combustible materials, gasoline and other flammable 

vapors and liquids.

Free flow of combustion and ventilating air to boiler and 

boiler room must not be restricted or blocked.

In event flow of combustion products through flueways 

or boiler venting system becomes blocked, flame roll-out 

safety switch will shut off main burner gas. See Figure 5. 

If this condition occurs, do not attempt to place boiler in 

operation. Contact qualified service agency.

It is suggested that qualified service agency be employed 

to make annual inspection of boiler and heating system. 

They are experienced in making inspection outlined above 

and in event repairs or corrections are necessary, they can 

make proper changes for safe operation of boiler.

Summary of Contents for DV

Page 1: ...the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Do not use this boiler if any part has been under water Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has ...

Page 2: ...TICE Indicates information which should be followed to ensure proper installation and operation WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided may result in minor or moderate injury Utica Boilers recommends all boiler maintenance be performed by a trained heating technician Before any...

Page 3: ...a qualified service technician Force or attempted repair may result in a fire or explosion Do not use this appliance if any part has been under D water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water E F Operating Instructions For Intermittent Pilot System STOP 1 Read the safety in...

Page 4: ...accumulated in the system Check the entire piping system and if any leaks appear have them repaired Figure 2 Circulator Many circulators like the one pictured in Figure 2 above require periodic servicing Motor usually has openings at each end to lubricate bearings Put about one half teaspoon of SAE 20 or 30 non detergent motor oil in each opening twice a year CAUTION Do Not Over Oil Many circulato...

Page 5: ...once a 7 month during heating season with few drops of non detergent motor oil SAE 20 or 30 Do not over oil Place sheet of heavy paper or similar material in 8 bottom of combustion chamber and brush down flue passageways Soot and scale will collect on paper and is easily removed with paper Visual check of main burner and pilot flames should be made at start of heating season and again in mid seaso...

Page 6: ... Orifices GAS VALVE ORIFICES BURNERS Figure 5 Boiler Front with Safety Switch COMBUSTION BURNER REMOVED BURNERS GAS VENT PIPE CHAMBER DOOR VALVE ADAPTER ROLL OUT SAFETY BURNER SWITCH JACKET FRONT PANEL Figure 7 Burners Pilot Flame IGNITION ELECTRODE 3 8 TO 1 2 IN FLAME ...

Page 7: ...7 NOTES ...

Page 8: ...TES Date of Installation Boiler Model Installed By Utica Boilers 2210 Dwyer Avenue Utica NY 13504 4729 Phone 315 797 1310 Fax 866 432 7329 e mail info ecrinternational com web site www ecrinternational com ...

Reviews: