26
15 - BURNER SETTINGS
Above settings are preliminary settings only� Final adjustments must be made using combustion test instruments
as previously outlined in the Operating Instructions
PN 240013073, Rev. A [08/31/2020]
TABLE 5 - CARLIN EZ-1/2 SETTINGS
BOILER
MODEL
BURNER
MODEL
FIRING
RATE
NOZZLE
MFR.
NOZZLE
TYPE
PUMP
PRESSURE
[PSI]
HEAD
BAR
AIR BAND
SETTING
AIR
SHUTTER
SFH-3085W(T)
EZ-1HP
0�85
DELAVAN
0�75 x 70 B
130
0�75
45%
BLANK
SFH-4100W(T)
EZ-1HP
1�00
DELAVAN
0�85 x 70 B
140
0�85/1�00
52%
BLANK
SFH-4125W(T)
EZ-1HP
1�25
DELAVAN
1�00 x 70 B
155
0�85/1�00
70%
BLANK
SFH-5160W(T)
EZ-2HP
1�60
DELAVAN
1�35 x 70 B
140
0�85/1�00
20%
3 SLOT
SFH-6185W(T)
EZ-2HP
1�85
DELAVAN
1�65 x 60 B
125
1�65/1�75
32%
3 SLOT
TABLE 3 -BECKETT AFG SETTINGS
BOILER
NO.
HEAD
TYPE
HEAD
SETTING
STATIC
PLATE
NOZZLE
PUMP
PRESSURE
[PSI]
AIR
BAND
AIR
SHUTTER
SFH-3085W(T)
L1
--
3⅜
0�75-60°B
140
0
8
SFH-4100W(T)
V1
0
2¾
0�85-60°B
140
0
6
SFH-4125W(T)
V1
0
2¾
1�10-60°B
140
1
8
SFH-5160W(T)
F12
--
2¾
1�35-70°B
140
1
10
SFH-6185W(T)
F12
--
--
1�65-70°B
125
2
10
TABLE 4 - RIELLO 40F5/40F10 SETTINGS
BOILER
MODEL
RIELLO
BURNER
MODEL
BURNER
INSERTION
[INCHES]
NOZZLE
PUMP
PRESSURE
[PSI]
TURBULATOR
SETTING
AIR
GATE
SETTING
SFH-3085W(T)
40F5
2�25
0�70x80°W
145
0�0
2�0
SFH-4100W(T)
40F5
2�25
0�85x80°W
145
1�0
2�55
SFH-4125W(T)
40F5
2�25
1�00x80°W
155
2�0
4�0
SFH-5160W(T)
40F5
2�25
1�35x60°W
145
4�0
5�75
SFH-6185W(T)
40F10
4�75
1�65x45°B
125
2�0
3�4