INSTALLATION SYSTEM PIPING
Check local codes
for maximum
distance from
floor or other
allowable safe
point of discharge
RELIEF VALVE
DISCHARGE
PIPING
Figure 2 - Safety Relief Valve Discharge Piping
1.
Refer to local codes and appropriate ASME Boiler
and Pressure Vessel Code for additional installation
requirements. Install safety relief valve using pipe
fittings provided with boiler. See Figure 2
2.
Install safety relief valve with spindle in vertical
position.
3.
Do not install shutoff valve between boiler and safety
relief valve.
4.
Install discharge piping from safety relief valve. See
Figure 2.
x
Use ¾” or larger pipe.
x
Use pipe suitable for temperatures of 375°F (191°C)
or greater.
x
Individual boiler discharge piping shall be independent
of other discharge piping.
x
Size and arrange discharge piping to avoid reducing
safety relief valve relieving capacity below minimum
relief valve capacity stated on rating plate.
x
Run pipe as short and straight as possible to location
protecting user from scalding and properly drain
piping.
x
Install union, if used, close to safety relief valve outlet.
x
Install elbow(s), if used, close to safety relief valve
outlet and downstream of union (if used).
x
Terminate pipe with plain end (not threaded).
WARNING
Burn and scald hazard. Safety relief valve could
discharge steam or hot water during operation.
Install discharge piping per these instructions.
!