54
Table 17 - Carlin (CHIMNEY VENT) Preliminary Burner Settings
Burner settings provided are for initial startup only. Final adjustments must be made using combustion test
instruments.
Table 17- CARLIN CHIMNEY VENT PRELIMINARY BURNER SETTINGS
Boiler
Model
Insertion
Depth
Firing
Rate
Combustion
Liner
Nozzle
Mfr.
Nozzle
Type
Pump
Pressure
[PSI]
Head Bar
Setting
Air Band
Setting
Rated
AFUE
Efficiency
[%]
4075
4.56"
0.75
Oval
Delavan
0.60 x 60B
160
1
22%
87.0
4090
4.56"
0.90
Oval
Delavan
0.75 x 70A
145
2
28%
86.0
5100
3.00"
1.00
None
Delavan
0.75 x 45B
175
0.75
36%
87.0
5120
3.00"
1.20
None
Delavan
1.00 x 60A
165
0.85/1.00
40%
86.0
6130
3.00"
1.30
V6
Delavan
1.00 x 70A
170
0.85/1.00
50%
87.0
6145
3.00"
1.45
V6
Delavan
1.10 x 70B
190
1.10/1.25
50%
86.0
Timings
Pre-purge
15 seconds
Post-purge
15 seconds
Boiler
Model
Carlin Oil
Burner
Model
ECR Oil
Burner
Part
Number
4075
EZ-Select
240013299
4090
EZ-Select
240013299
5100
EZ-LF
240013406
5120
EZ-LF
240013406
6130
EZ-LF
240013408
6145
EZ-LF
240013408
17 - OIL BURNER, NOZZLE, & AIR SETTINGS
PN 240013415 REV A [08/15/2021]