Phone (828)323-8914
Fax
(828)323-8410
Web
101 33
rd
Street Drive SE · Hickory, NC 28602
© 2018 Utility Solutions Inc.
C-00804 USJJ-001/2 Instruction Manual (9-7-18)
!
!
DANGER
Contact with high voltage will cause death or grievous personal
injury to the operator. Only use this device in conjunction with
safe operating practices around energized lines and equipment.
!
!
WARNING
Carefully read and fully understand the INSTRUCTION
MANUAL prior to operating, maintaining or testing this
device. Improper operation, handling or maintenance of this
device can result in death, grievous personal injury and or
equipment damage.
Jack Jumper™ Cutout Bypass Tool
!
!
WARNING
Follow safe work procedures and practices when utilizing this
device. Failure to use this device in a safe manner can result in
death, grievous personal injury and or equipment damage.
!
!
WARNING
These instructions are not intended to replace or be a substitute
for proper safety training procedures. Failure to select the proper
tool in regards to minimum system requirements can result in
death, grievous personal injury and or equipment damage.
!
!
WARNING
Only trained and qualified personnel should operate, inspect
and maintain this device.
Product Description
The Jack Jumper™ Cutout Bypass Tool permits a safe and quick method to bypass an overhead cutout without the tedious use of bulky jumper
cables. The tool is indispensable for fuse coordination tasks and permits easy bypass of an underground dip. The Jack Jumper™ Cutout Bypass
Tool saves time and money, eliminates risk of service interruption and prevents accidental cross phasing.
The primary purpose of the Jack Jumper™ Cutout Bypass Tool is to temporarily bypass a cutout fuse door during fuse coordination. The Jack
Jumper™ Cutout Bypass Tool is rated at 100 Amps continuous AC current without exceeding a 40°C temperature rise.
Installation and removal of the Jack Jumper™ Cutout Bypass Tool is done with a shotgun stick.
!
!
WARNING
Never install or remove a Jack Jumper™ Cutout Bypass Tool on
an open cutout.
USJJ-001 15 kV Cutout Bypass Tool
USJJ-002 27 kV Cutout Bypass Tool
Perpendicular Ring
Spring Mechanism
In-Line Ring
Attachment Hooks