GenOverVoltFault
GenUnderVoltFault
GenOverFreqFault
GenUnderFreqFault
D03
D04
D05
D06
Pv1HwOverCurrFault
Pv2HwOverCurrFault
Pv3HwOverCurrFault
Pv4HwOverCurrFault
Pv5HwOverCurrFault
Pv6HwOverCurrFault
Pv7HwOverCurrFault
Pv8HwOverCurrFault
Pv9HwOverCurrFault
Pv10HwOverCurrFault
Pv11HwOverCurrFault
Pv12HwOverCurrFault
Pv1SwOverCurrFault
Pv2SwOverCurrFault
Pv3SwOverCurrFault
Pv4SwOverCurrFault
Pv5SwOverCurrFault
Pv6SwOverCurrFault
Pv7SwOverCurrFault
Pv8SwOverCurrFault
GenOverVoltFault
GenUnderVoltFault
GenOverFreqFault
GenUnderFreqFault
E01
E02
E03
E04
E05
E06
E07
E08
E09
E10
E11
E12
E13
E14
E15
E16
E17
E18
E19
E20
Type of Fault Code
Name
Description
Recommend Solution
D01
Off-grid Fault
DC Fault
UpsOverPowerFault
PV current over, triggered
by Software logic.
• Power off, power on then restart.
• If those faults occurs continuously and
frequently, please ask help for local
distributors.
PV current over, triggered
by hardware protection
circuit
• Power off, then restart (Ref. Chapter8).
• If those faults occurs continuously and
frequently, please ask help for local
distributors.
• Adjust generator running parameters,
make the output voltage, frequency in
allowed range.
• If this fault occurs continuously and
frequently, please ask help for local
distributors.
0ff-grid load over
• Reduce loads.
• If sometimes overload, it can be
ignored, when generation power enough
can be recovery.
• If those faults occurs continuously and
frequently, please ask help for local
distributors.
D02
GridConflictFault
Grid connected to Back-up
terminal
• Check the off-grid port connection
correct, disconnect both off-grid and grid
ports.