Installation Instruction
Product Code: SKU 7817
Product Description: SELF TEST-LED EMERGENCY EXIT BOX WITH ARROW UP LEGEND
Routine Testing
Specification
Testing Record
Testing should be carried out in accordance with the recommendations of BS5266 & EN50172.
1.
Do not switch off unswitched mains supply after installation. If interruption is unavoidable, the batteries must be
disconnected or damage to the batteries may occur. Leave the luminaire on continuous charge for 24 hours.
2.
A monthly functional test should be conducted manually.
3.
Annually, a full three hour duration test should be conducted manually.
4.
Batteries should be replaced when the luminaire no longer meets the 3 hours duration performance.
5.
Testing is performed by interrupting the unswitched supply for the test duration manually or self-test function
complying with IEC62034.
During testing the luminaire should remain illuminated in emergency mode.
6.
Ensure that the ‘charge indicator’ is ‘ON’ during ‘Charging Mode’.
If the charge indicator (LED) is unlit, this signifies a fault.
7.
Replace faulty light source and batteries immediately.
To assist with this testing, a test record is included below.
To increase the chance of a fault being reported between monthly tests, it is desirable that staff are made aware
of the purpose of the indicator.
1
2
3
4
5
6
7
8
9
10
11
12
Functional/Duration
Month
Year 1
Year 2
Year 3
Year 4
Year 5
Product: _______________ Location:_____________ Installation Date:____________
Emergency Power:
Viewing Distance:
EM Duration:
Charging Time:
Ambient Temp:
Emergency Mode:
Function:
Battery:
Warranty:
<4W
30M(EU ) / 24M(AU )
1H/3H/8H
24 hours
5-45°C
Maintained
Self-test
LiFePO4 3.2V 1.5Ah
4 years (battery 2 years )
4
20