Specifications for Self Test
Function Test
The function test is carried out every month for 3 minutes. It will check the connection of battery,
battery discharging and the connection of LED module.
Duration Test
An initial duration test is carried out at first power on, but after 24 hours charging. The yearly
duration test is carried out for 3 hours on one day within the 300th day to the 365th day every
year. It will also check the connection of battery and LED module.
A bi-colour indicator will indicate the normal and abnormal status. Green is for conditions are
normal and red for the faulty conditions.
LED Colour
Status
On Time
(Seconds)
Off Time
(Seconds)
Description
Green
Permanent on
/
/
Normal status when mains connected
Slow flash
1s
1s
Duration test running
Fast flash
0.2s
0.2s
Function test running
Normal flash
three times only
0.5s
0.5s
Time reset
Red
Permanent on
/
/
Battery failure
Slow flash
1s
1s
Lamp failure
Fast flash
0.2s
0.2s
Duration failure - the capacity of the
battery is not enough
Both Off
Off
/
/
Emergency mode
A test switch is applied for different functions activated manually.
Duration
Function
Press for <2s
Simulate emergency mode
Press for 3-5s
Start duration test manually. The test can be aborted by pressing off (1-2s).
Press for 5-8s
Start Function test manually for 60s.
The test can be aborted by pressing off (1-2s).
Press for >10s
Time Reset