Specifications for Self Test 

 

 

Function Test 

The function test is carried out every month for 3 minutes. It will check the connection of battery, 

battery discharging and the connection of LED module.  

 

Duration Test 

An initial duration test is carried out at first power on, but after 24 hours charging. The yearly 

duration test is carried out for 3 hours on one day within the 300th day to the 365th day every 

year. It will also check the connection of battery and LED module. 

 

 

 

A bi-colour indicator will indicate the normal and abnormal status. Green is for conditions are 

normal and red for the faulty conditions. 

 

LED Colour 

Status 

On Time 

(Seconds) 

Off Time 

(Seconds) 

Description 

Green 

 

Permanent on 

Normal status when mains connected 

 

Slow flash 

1s 

1s 

Duration test running 

 

Fast flash 

0.2s 

0.2s 

Function test running 

 

Normal flash 

three times only 

0.5s 

0.5s 

Time reset 

 

 

Red 

 

Permanent on 

Battery failure 

 

Slow flash 

1s 

1s 

Lamp failure 

 

Fast flash 

0.2s 

0.2s 

Duration failure - the capacity of the 

battery is not enough 

Both Off 

 

Off 

Emergency mode 

 

A test switch is applied for different functions activated manually. 

 

Duration 

Function 

Press for <2s 

Simulate emergency mode 

Press for 3-5s 

Start duration test manually. The test can be aborted by pressing off (1-2s). 

Press for 5-8s 

Start Function test manually for 60s. 

The test can be aborted by pressing off (1-2s). 

Press for >10s 

Time Reset 

 

 

 