GRID CONNECTION
VT series inverter are designed for single phase grid. Voltage is 220/230/240V, frequency
is 50/60Hz. Other technical requests should comply with the requirement of the local
public grid.
Micro-breaker should be installed between inverter and grid, any load should not be connect
-
ed with inverter directly.
CONNECTION STEPS
Step 1. Check the grid voltage.
1.Check the grid voltage and compare with the permissive voltage range
(Please refer to technical data).
2.Disconnect the circuit board from all the phases and secure against re-connection.
10mm
Crimp!
12AWG
insert
Step3
Step4
Step5
Table of cable and Micro-breaker recommended
MODEL
VT-6608303
E VERSION CABLE
4-5 mm²
E VERSION MICRO-BREAKER
20A
I VERSION CABLE
6-8mm²
I VERSION MICRO-BREAKER
40A