- 46 -

PARAMETER

VALUE

DESCRIPTION

DEFAULT

MEMO

SP.AP

Pedestrian Start during the partial opening phase

This menu allows fixing the control unit conduct in case it receives a 
Pedestrian Start command during the partial opening phase.

WARNING: a Start command in any phase of partial opening will 
cause the total opening; the Start Pedestrian command is always 
ignored during a total opening

PAUS

PAUS

The gate stops and goes to pause

ChiU

The gate immediately starts closing

no

The gate goes on with the opening phase (command is ignored)

Ch.AU

Automatic closing

In automatic mode, the control unit automatically recloses the gate on 
expiry of the time limit set in this menu

no

no

Function deactivated

0.5” - 20.0’

The gate recloses after the set time
(adjustable time from 0,5” to 20.0’)

Ch.tr

Closure after passage

During the automatic operation, the pause count down starts from the set 
up value each time a photocell operates during the pause.
If the photocell operates during the opening time, this time will be
immediately stored as pause time.
This function allows having a fast closing as soon as transit through the 
gate is completed, therefore, a time shorter than 

Ch.AU 

is generally used

no

no

Function deactivated

0.5” - 20.0’

The gate recloses after the set time
(adjustable time from 0,5” to 20.0’)

PA.tr

Pause after transit

no

Si

In order to let the gate open for the shortest possible time, it is possible
to stop the gate once the passage before the photocells is detected.
If the automatic working is enabled, the time of the pause is 

Ch.tr

no

Function deactivated

LUCi

Courtesy lights

This menu allows setting the automatic operating of the courtesy lights 
during the opening cycle of the gate

t.LUC

t .LUC

Timed function (from 0 to 20’)

1 ’00

no

Function deactivated

CiCL

On for the entire duration of the cycle

AUS

Auxiliary channel

This menu allows setting the operating of the relay of the lighting of the 
courtesy lights by means of a remote control stored on the channel 4 of 
the receiver

Mon

t iM

Timed function (from 0 to 20’)

biSt

Bistable operation

Mon

Monostable operation

LP.PA

Blinker during pause time

no

no

Function deactivated

Si

The blinker will be on during the pause time too (gate open with
automatic closure active)

Summary of Contents for 23E011

Page 1: ...PESO GB 230V ELECTRO MECHANICAL IRREVERSIBLE RACK ACTUATOR FOR SLIDING GATES UP TO 2500 KG F OPERATEUR ELECTROMECANIQUE 230V IRREVERSIBLE A CREMAILLERE POUR PORTAILS COULISSANTS JUSQU A 2500 KG DE POI...

Page 2: ...380 mm 380 mm 103 mm 377 mm 250 mm 285 mm 86 mm 78 mm 86 mm 250 mm 63 mm 3 mm 80 mm...

Page 3: ...OTOCELLULE 4 7 COSTE SENSIBILI 4 8 ANTENNA 4 9 COLLEGAMENTI ELETTRICI 4 10 RICEVITORE AD INNESTO 4 11 INTERFACCIA ADI 5 PANNELLO DI CONTROLLO 5 1 DISPLAY 5 2 USO DEI TASTI PER LA PROGRAMMAZIONE 6 ACCE...

Page 4: ...n ambiente e atmosfera esplosivi presenza di gas o fumi infiammabili costituiscono un grave pericolo per la sicurezza Non eseguire modifiche su nessuna parte dell automatismo o degli accessori ad esso...

Page 5: ...limitato numero di persone autorizzato all uso e la chiusura non in un area pubblica Un esempio di questo tipo sono i cancelli all interno delle aziende i cui fruitori sono solo i dipendenti o una pa...

Page 6: ...lli scorrevoli destinato ad essere incorporato in un cancello scorrevole per costituire una macchina ai sensi della Direttiva 2006 42 CE Tale macchina non potr essere messa in servizio prima di essere...

Page 7: ...20 C 55 C 20 C 55 C Peso del motore 19 Kg 21 Kg Protezione IP44 IP44 Carico max accessori alimentati a 24 Vac 10W 10W Fusibili di protezione F1 8A F1 8A 2 CARATTERISTICHE TECNICHE 10 00 15 00 20 00 25...

Page 8: ...te in bolla e parallela cancello 5 Attendere la completa presa del calcestruzzo 6 Svitare i 4 dadi che tengono la base unita alle zanche e posizionare il motore sulla piastra 7 Inserire i 4 grani con...

Page 9: ...cello molto pesante si consiglia l utilizzo di una cremagliera M4 22x22 cod 162324 3 3 FISSAGGIO DEL MOTORE Verificare i seguenti punti 1 Il motore deve essere in bolla e parallelo al cancello 2 La di...

Page 10: ...massima apertura e di massima chiusura il magnete rimanga posizionato in corrispondenza del sensore magnetico posto dietro la calotta il pi possibile vicino alla stessa I magneti in dotazione sono ap...

Page 11: ...mettitore Modulo ricevitore Fotocellule Lampeggiante COMPONENTI ACCESSORI AGGIUNTIVI 3 5 SBLOCCO MOTORE In caso di mancanza di corrente elettrica il cancello pu essere sbloccato agendo sul motore 1 Ap...

Page 12: ...ART P la cui funzione dipende dalla modalit di funzionamento programmata parametro Strt mATTENZIONE se vengono utilizzati dispositivi a comando mantenuto spire magnetiche timer rilevatori di presenza...

Page 13: ...nzionamento 4 7 COSTE SENSIBILI A seconda del morsetto a cui vengono collegate la centrale suddivide le coste sensibili in due categorie Coste di tipo 1 In caso di intervento delle coste di tipo 1 dur...

Page 14: ...VER FUSE MAINS OVERLOAD L LINE N NEUTRAL LAMP 230V MAX 40W COURTESY LIGHT CONTACT START START P STOP COM PHOTO 1 PHOTO 2 EDGE 1 EDGE 2 COM 24V 10W 24V Photo Edge Test GND ANT A1 A2 mCollegare a terra...

Page 15: ...ay della centrale nel modo seguente ALLARME FOTOCELLULA il segmento in alto si accende il cancello si ferma quando l allarme cessa riparte in apertura ALLARME COSTA il segmento in basso si accende il...

Page 16: ...menu di configurazione premendo il tasto h si attiva il comando START e premendo il tasto i si attiva il comando START PEDONALE Esistono tre tipologie di voci di menu Menu di funzione Menu di tempo Me...

Page 17: ...e alla direzione del cancello e alle sicurezze installate Per la posizione delle voci all interno del menu e per le opzioni disponibili per ciascuna voce fare riferimento al capitolo 13 3 Avviare il c...

Page 18: ...o abilitato sul display viene visualizzato il valore suggerito per la soglia del sensore Se non viene eseguita nessuna operazione per 20 secondi la centrale esce dalla fase di programmazione senza sal...

Page 19: ...zatore leggere il numero di cicli mancanti al prossimo intervento di manutenzione e programmare il numero di cicli mancanti al prossimo intervento di manutenzione nell esempio la centrale ha completat...

Page 20: ...ra SX Il cancello apre verso sinistra P APP Apertura parziale 25 0 1 00 Percentuale della corsa che il cancello esegue in caso di apertura comandata con Start Pedonale t PrE Tempo prelampeggio 1 0 0 5...

Page 21: ...tore scende sotto il valore impostato la centrale rileva un allarme Il valore visualizzato in cm s Quando interviene il sensore il cancello si ferma e viene comandato in direzione inversa per 3 second...

Page 22: ...sa Questa funzione permette di avere una rapida chiusura dopo il transito attraverso il cancello per cui solitamente si utilizza un tempo inferiore a Ch AU no no Funzione disabilitata 0 5 20 0 Il canc...

Page 23: ...per le fotocellule di tipo 2 cio non attive in apertura CFCh CFCh Ingresso abilitato anche a cancello fermo la manovra di apertura non inizia se la fotocellula interrotta Ch Ingresso abilitato solo in...

Page 24: ...la centrale 2 Prima di agire sulla centrale togliere corrente tramite il sezionatore installato sulla linea di alimentazione e rimuovere il morsetto di alimentazione 3 Controllare se il fusibile F1 br...

Page 25: ...litate da men siano effettivamente installate Errore 6 Durante la manovra il motore si ferma e sul display compare la scritta Err6 Significa che ci sono problemi di comunicazione con la scheda inverte...

Page 26: ...ifiche previste dovrebbero riguardare almeno la perfetta efficienza di tutti i dispositivi di segnalazione la perfetta efficienza di tutti i dispositivi di sicurezza la misurazione delle forze operati...

Page 27: ...utilizzo domestico ma questo periodo pu variare in funzione dell intensit d uso Qualunque intervento di controllo manutenzione o riparazione deve essere eseguito solo da personale qualificato Anche s...

Page 28: ...ITALIANO 26...

Page 29: ...4 5 STOP 4 6 PHOTOCELLS 4 7 SAFETY RIBBONS 4 8 EXTERNAL AERIAL 4 9 ELECTRICAL CONNECTION 4 10 PLUG IN RECEIVER 4 11 ADI INTERFACE 5 CONTROL PANEL 5 1 DISPLAY 5 2 USE OF THE KEYS FOR PROGRAMMING 6 ACC...

Page 30: ...s a serious safety hazard Do not make any modifications to any part of the automation device or the accessories connected to it unless described in this manual Any other modifications will void the wa...

Page 31: ...are authorised for use and closure is not in a public area Examples of this type are gates inside business premises where the sole users are employees or a part of them who have been suitably informed...

Page 32: ...talled on sliding gates to create a machine according to the provisions of the Directive 2006 42 EC The machinery must not be put into service until the final machinery into which it has to be incorpo...

Page 33: ...temperature 20 C 55 C 20 C 55 C Weight 19 Kg 21 Kg Protection IP44 IP44 Maximum load on 24 VAC attachments 10W 10W Protection fuses F1 8A F1 8A 2 TECHNICAL DATA 10 00 15 00 20 00 25 00 30 00 35 00 40...

Page 34: ...5 Wait for the complete setting of the concrete 6 Unscrew the bolts fixing the base to the clamps and put the motor on the plate 7 Insert the 4 grains with their nuts in the proper place Adjust the 4...

Page 35: ...x22 rack code 162324 3 3 FIXING OF THE MOTOR Check the following points 1 the motor must be on a levelled surface and perfectly parallel to the gate 2 the distance between pinion and rack must be 1 or...

Page 36: ...g and closing limit positions the magnet be positioned next to the magnetic sensor behind the hood as near as possible to the hood The supplied magnets have been colored differently in order to be dis...

Page 37: ...of edges WES sensors Motor Transmitter Receiving module Photocells Flashing light COMPONENTS ADDITIONAL ACCESSORIES 3 5 MOTOR OVERRIDING SYSTEM In case of absence of current the gate can be released...

Page 38: ...ds on the programmed operation modes see Strt item of programming menu mWARNING If you use maintained command devices magnetic loop detectors timers presence detectors etc clock mode must be used para...

Page 39: ...carry out the operation test 4 7 SAFETY RIBBONS The control unit considers two kinds of safety ribbons depending on the terminal to which they are connected Type 1 When type 1 safety ribbons operate d...

Page 40: ...M10 M11 M12 RECEIVER FUSE MAINS OVERLOAD L LINE N NEUTRAL LAMP 230V MAX 40W COURTESY LIGHT CONTACT START START P STOP COM PHOTO 1 PHOTO 2 EDGE 1 EDGE 2 COM 24V 10W 24V Photo Edge Test GND ANT A1 A2 mC...

Page 41: ...on the control unit display as follows PHOTOCELL ALARMS the upper segment comes on the gate stops moving when the alarm stops opening restarts EDGE ALARM the lower segment comes on inverts motion of t...

Page 42: ...the START command pressing the i key activates the PEDESTRIAN START command There are the following three kinds of menu items Function menu Time menu Value menu Function menu setup Function menus all...

Page 43: ...8 2 Set items dir StoP Fot1 Fot2 CoS1 CoS2 according to the safety devices installed on the gate For the position of the item menus inside the main menu and for the options related to each item menu r...

Page 44: ...eed 5 If the AMPEROMETRIC obstacle sensor was enabled the display shows the suggested value for sensor threshold If no operations are performed for 20 seconds the control unit exits the programming ph...

Page 45: ...to read the totalizing counter how to read the number of cycles before the next service is required as well as how to program the number of cycles before the next request for service as for the exampl...

Page 46: ...rds P APP Partial opening 25 0 1 00 The percentage of the path the gate performs in the case of opening using the Pedestrian Start command t PrE Pre blinking time 1 0 0 5 1 00 Before any gate movement...

Page 47: ...ol unit raises an alarm The value shown is in cm s When the sensor intervenes the gate stops and is operated in the reverse direction for 3 seconds to remove the obstacle The next start command restar...

Page 48: ...iately stored as pause time This function allows having a fast closing as soon as transit through the gate is completed therefore a time shorter than Ch AU is generally used no no Function deactivated...

Page 49: ...CFCh Input enabled even at standstill gate too the opening movement does not start if photocell is interrupte Ch Input enabled for the closing phase only WARNING if you select this option you must dis...

Page 50: ...ecting switch on the power line and remove the power supply terminal 2 Be sure that there is no voltage break upstream the control unit 3 Check whether the fuse is burnt out if so replace it with same...

Page 51: ...edges enabled from the menu are installed Error 6 During the manoeuvre the motor stops and the display shows Err6 It means that there are communication problems with the inverter board If the problem...

Page 52: ...each maintenance operation is six months the checks involved should at least relate to the perfect efficiency of all warning devices the perfect efficiency of all safety devices measurement of the ga...

Page 53: ...ay vary depending on the intensity of use Any inspection maintenance or repairs should only be performed by qualified personnel Even if you think you know how do not modify the system and the automati...

Page 54: ...ENGLISH 52...

Page 55: ...4 7 BARRES PALPEUSES 4 8 ANTENNE 4 9 RACCORDEMENTS LECTRIQUES 4 10 RECEPTEUR EMBROCHABLE 4 11 INTERFACE ADI 5 PANNEAU DE CONTROLE 5 1 DISPLAY 5 2 UTILISATION DES TOUCHES DE PROGRAMMATION 6 ACC S AUX P...

Page 56: ...grave danger pour la s curit Ne pas ex cuter de modifications sur aucune partie de l automatisme ou sur ses accessoires si cela n est pr vu dans le pr sent manuel Toute autre modification fera d choir...

Page 57: ...peut citer comme exemple de ce type les portails l int rieur des soci t s dont les utilisateurs sont les seuls employ s ou partie d entre eux et ont t sp cialement inform s GROUPE 2 Seul un nombre lim...

Page 58: ...our portails coulissants a t con u pour tre incorpor dans un portail coulissant en vue de former une machine conform ment la Directive 2006 42 CE Cette machine ne pourra pas tre mise en service avant...

Page 59: ...re de travail 20 C 55 C 20 C 55 C Poids 19 Kg 21 Kg Protection IP44 IP44 Charge max accessoires aliment s 24 VAC 10W 10W Fusibles de protection F1 8A F1 8A 2 CARACT RISTIQUES TECHNIQUES 10 00 15 00 20...

Page 60: ...ON v rifier que la plaque soit parfaitement de niveau et parall le au portail 5 Attendre la prise compl te du b ton 6 D visser les 4 crous qui tiennent la base reli e aux tires fonds et positionner le...

Page 61: ...ortail est tr s lourd on conseille d utiliser une cr maill re M4 22x22 cod 162324 3 3 FIXATION DU MOTEUR V rifier les points suivants 1 Le moteur doit tre en bulle et parall le au portail 2 La distanc...

Page 62: ...les positions d ouverture maximale et de fermeture maximale l aimant reste positionn hauteur du capteur magn tique plac derri re le bo tier le plus pr s possible de ce m me bo tier Les aimants fourni...

Page 63: ...OMPOSANTS AUTRES ACCESSOIRES 3 5 D BLOCAGE MOTEUR En cas d absence de courant lectrique le portail peut tre galement d verrouill en agissant sur le moteur 1 Ouvrir la protection de la serrure J se tro...

Page 64: ...d pend de la modalit de fonctionnement programm e param tre Strt mATTENTION si des dispositifs commande maintenue sont utilis s voyants magn tiques minuterie d tecteurs de pr sence etc il faut utilis...

Page 65: ...intervention des barres de type 1 pendant l ouverture du portail l armoire inverse le mouvement pendant 3 secondes et puis se bloque en cas d intervention des barres du type 1 pendant la fermeture du...

Page 66: ...M10 M11 M12 RECEIVER FUSE MAINS OVERLOAD L LINE N NEUTRAL LAMP 230V MAX 40W COURTESY LIGHT CONTACT START START P STOP COM PHOTO 1 PHOTO 2 EDGE 1 EDGE 2 COM 24V 10W 24V Photo Edge Test GND ANT A1 A2 mR...

Page 67: ...t en haut s allume le portail s arr te quand l alarme cesse il repart en ouverture ALARME BARRE PALPEUSE le segment en bas s allume dans le portail il inverse le mouvement pendant 3 secondes ALARME ST...

Page 68: ...ation en appuyant sur la touche h la commande START est activ e en appuyant sur la touche i la commande START PI TON est activ e Il existent trois types de voix de menu Menu de fonction Menu de temps...

Page 69: ...ortail et des s curit s install es sur le portail Pour la position des rubriques l int rieur du menu et pour les options disponibles pour chaque rubrique il faut faire r f rence au chapitre 13 3 D mar...

Page 70: ...TRIQUE a t habilit l cran affiche la valeur sugg r e pour le seuil du capteur Si aucune des op ration n est ex cut e pendant 20 secondes l armoire de commande quitte la phase de programmation sans sau...

Page 71: ...t configur sur StAn la commande Start g n r e depuis les bornes ou depuis la t l commande permet d ouvrir et de fermer alternativement la grille la diff rence du mode homme mort normal 12 LECTURE DU C...

Page 72: ...P APP Ouverture partielle 25 0 1 00 Pourcentage de la course ex cut e par la grille en cas d ouverture command e avec l option Start Pi ton t PrE Temps de pr avis 1 0 0 5 1 00 Avant chaque mouvement d...

Page 73: ...enu permet de r gler la vitesse du portail pendant la phase de ralentissement La valeur affich e est en cm s Quand le capteur intervient le portail s arr te et il est command en direction contraire pe...

Page 74: ...terviens pendant l ouverture viens imm diatement charg ce temps comme temps de pause Cette fonction permet d avoir une fermeture rapide apres le si on r gle un temps inferieur Ch AU no no Fonction d s...

Page 75: ...ion de sens pendant la fermeture et emp che les commandes d ouverture lorsque le portail est l arr t Ch L entr e PHOTO2 provoque uniquement l inversion de sens pendant la fermeture Attention si on cho...

Page 76: ...au du tableau lectrique et d brocher le bornier d alimentation 2 S assurer qu il n y a pas de coupure secteur en amont de la platine 3 Contr ler si le fusible F1 est br l En ce cas le remplacer par un...

Page 77: ...ivement install es Erreur 6 Pendant la manoeuvre le moteur s arr te et le message Err6 appara t sur l cran Cela signifie qu il y a des probl mes de communication avec la carte inverter Si le probl me...

Page 78: ...ations pr vues devraient concerner au moins l efficacit parfaite de tous les dispositifs de signalisation l efficacit parfaite de tous les dispositifs de s curit la mesure des forces op rationnelles d...

Page 79: ...mais cette fr quence peut varier en fonction de l intensit d usage Toutes interventions de contr le entretien ou r paration doivent tre effectu es par un personnel qualifi M me si vous pensez en tre...

Page 80: ...FRAN AIS 78...

Page 81: ...DE SEGURIDAD 4 8 ANTENA EXTERNA 4 9 CONEXIONES ELECTRICAS 4 10 RECEPTOR ENCHUFABLE 4 11 INTERFAZ ADI 5 PANEL DE CONTROL 5 1 DISPLAY 5 2 USO DE LAS TECLAS PARA LA PROGRAMACI N 6 ACCESO A LAS CONFIGURAC...

Page 82: ...conectados a estos si no est n previstas en el presente manual Cualquier otra modificaci n har que se anule la garant a del producto Las fases de instalaci n se deben realizar evitando los d as lluvio...

Page 83: ...erre no est en un rea p blica Un ejemplo de este tipo son las cancelas dentro de las empresas cuyos usuarios son s lo los empleados o una parte de ellos que han sido adecuadamente informados GRUPO 2 S...

Page 84: ...500 I FORTECO2500 I M Descripci n Servomotor electromec nico para puertas correderas est destinado a ser incorporado en una puerta corredera para constituir una m quina conforme a la Directiva 2006 42...

Page 85: ...55 C 20 C 55 C Peso motor 19 Kg 21 Kg Grado de protecci n IP44 IP44 Carga m x accesorios alimentados a 24 VAC 10W 10W Fusibles de protecci n F1 8A F1 8A 2 CARACTERISTICAS TECNICAS 10 00 15 00 20 00 25...

Page 86: ...da y paralela a la puerta 5 Esperar que el hormigon frag e completamente 6 Desenroscar las 4 tuercas que tienen la base unida a las pletinas y colocar el motor sobre la placa 7 Regular los 4 esp rrago...

Page 87: ...rta es muy pesada es aconsejable usar una cremallera M4 22x22 cod 162324 3 3 FIJACION DEL MOTOR Verificar los siguientes puntos 1 El motor debe estar nivelado y paralelo a la puerta 2 La distancia ent...

Page 88: ...iciones de m xima apertura y de m ximo cierre el im n permanezca posicionado en correspondencia con el sensor magn tico colocado detr s de la tapa lo m s pr ximo posible a la misma Los imanes en dotac...

Page 89: ...o Sensores WES Motorreductor Emisor M dulo receptor Fotoc lulas L mpara de se alizaci n COMPONENTES ACCESORIOS ADICIONALES 3 5 DESBLOQUEO MOTOR En caso de falta de corriente el ctrica la puerta puede...

Page 90: ...one de dos entradas de activaci n START y START P Su funcionamiento depende de la modalidad programada par metro Strt mATENCI N si se utilizan dispositivos de mando mantenido espiras magn ticas tempor...

Page 91: ...uncionamiento 4 7 BANDAS DE SEGURIDAD Seg n el borne donde est n conectadas el cuadro divide las bandas de seguridad en dos categor as Banda del tipo 1 En caso de intervenci n de las bandas del tipo 1...

Page 92: ...12 RECEIVER FUSE MAINS OVERLOAD L LINE N NEUTRAL LAMP 230V MAX 40W COURTESY LIGHT CONTACT START START P STOP COM PHOTO 1 PHOTO 2 EDGE 1 EDGE 2 COM 24V 10W 24V Photo Edge Test GND ANT A1 A2 mConectar a...

Page 93: ...LULA el segmento de arriba se enciende la cancela se para cuando la alarma cesa la cancela vuelve a abrirse ALARMA COSTA el segmento de abajo se enciende la cancela invierte su movimiento durante 3 se...

Page 94: ...de configuraci n pulsando la tecla h se activa el mando START pulsando la tecla i se activa el mando START PEATONAL Existen tres tipos de voces de men Men de funci n Men de tiempo Men de valor Progra...

Page 95: ...CoS1 CoS2 en funci n de la direcci n de la cancela y de los dispositivos de seguridad instalados Para la posici n de las opciones dentro del men y para los valores programables en cada opcion hacer r...

Page 96: ...antalla se visualiza el valor sugerido para el umbral del sensor Si no se efect a ninguna operaci n durante 20 segundos la central sale de la fase de programaci n sin guardar el valor sugerido 6 El va...

Page 97: ...egundo la pausa entre los comandos debe durar al menos 1 segundo 1 1 1 T 1 1 1 La cuarta orden de START activa la cancela en modo HOMBRE PRESENTE para mover la cancela hay que mantener activa la orden...

Page 98: ...bre hacia la izquierda P APP Apertura parcial 25 0 1 00 Porcentaje de la carrera que la cancela efect a en caso de apertura mandada con Start Peatonal t PrE Tiempo de predestello 1 0 0 5 1 00 Antes de...

Page 99: ...ad del motor es inferior al valor ajustado la central detecta una alarma El valor visualizado est en cm s Cuando interviene el sensor la puerta se detiene y se acciona en direcci n inversa durante 3 s...

Page 100: ...nte la apertura inmediatamente se carga este tiempo como tiempo de pausa Esta funci n permite un cierre r pido despu s del transito del veh culo consiguiendo utilizar un tiempo inferior a Ch AU no no...

Page 101: ...Entrada habilitada incluso a puerta parada la maniobra de apertura no empieza si la fotoc lula est interrumpida Ch Entrada habilitada solo en cierre Atenci n si se elige esta opci n es necesario desh...

Page 102: ...borne de alimentaci n 2 Asegurarse de que no haya una interrupci n de corriente antes del cuadro 3 Controlar si el fusible F1 est quemado En este caso sustituirlo con uno del mismo valor El led OVERLO...

Page 103: ...e de que las bandas de seguridad que han sido habilitadas a menu est n realmente instaladas Error 6 Durante la maniobra el motor se detiene y en la pantalla aparece el mensaje Err6 Significa que hay p...

Page 104: ...s a la perfecta eficiencia de todos los dispositivos de indicaci n la perfecta eficiencia de todos los dispositivos de seguridad la medici n de las fuerzas operativas de la cancela la lubricaci n de l...

Page 105: ...n plan de mantenimiento a efectuar cada 6 meses para un uso normal dom stico pero este per odo puede variar en funci n de la intensidad de uso Cualquier intervenci n de control mantenimiento o reparac...

Page 106: ...ESPA OL 104...

Page 107: ......

Page 108: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY Tel 39 0172 812411 Fax 39 0172 84050 info v2home com www v2home com...

Reviews: