DISPLAYING
DESCRIPTION
SOLUTION
MAINS led does not switch
on
It means that there is no voltage on control
unit card.
1.
Before acting on the control unit, disconnect through
the disconnecting switch on the power line and
remove the power supply terminal.
2.
Be sure that there is no voltage break upstream the
control unit.
3.
Check whether the fuse is burnt-out, if so replace it
with same value.
OVERLOAD led is on
It means that there is an overload on
accessory power supply.
1.
Remove the extractable part containing terminals
M1 -
M12
. OVERLOAD led will switch off.
2.
Remove the overload cause.
3.
Reinsert the terminal board extractable part and check
that this led is not on again.
Too long pre-blinking
When a Start command is given and the
blinker switches on immediately but the
gate is late in opening
It means that the setup cycle count down expired and the
control unit shows that service is required
Slow movement of the gate
while closing
When a Start command is given the gate
will be closed at slow speed until the closed
range limit and after resumes normal
operation
This condition can occur when the motor encoder must
be realigned.
This anomaly can occur due to power failure with
the gate open or due to other factors related to the
malfunctioning of the gate.
The display shows
Err2
When a start command is given the gate
won’t open.
It means that TRIAC test failed.
Before sending the control unit to V2 S.p.A. for repair, be
sure that motors have been properly connected.
The display shows
Err3
When a start command is given the gate
won’t open.
It means that the photocell test failed.
1.
Be sure that no obstacle interrupted the photocell
beam when the Start command was given.
2.
Be sure that photocells, as enabled by their relevant
menus, have been installed actually.
3.
If you have photocells 2, be sure that
Fot2
menu
item is on
CF.Ch
.
4.
Be sure that photocells are powered and working:
interrupt the ray and check that the photocell segment
on the display changes position.
The display shows
Err4
When a Start command is given and the
gate does not open
This anomaly can occur when in one of the following
conditions:
1.
If a START command is sent with the motor released.
2.
During the self-learning cycle if there are any problems
with the range limits.
Check the direction of the magnets, if they are
backwards, they should be removed and inverted.
If the magnets are installed correctly, it means that
the limit switch sensor is damaged or the cabling
connecting the sensor to the central control unit is
broken/damaged.
Change the end of stroke sensor or the broken wiring.
3.
During normal operation. If the error persists send the
control unit to V2 S.p.A. for repair.
14 - OPERATION DEFECTS
This paragraph shows some possible operation defects, along
with their cause and applicable remedy.
Some anomalies are signalled using a message on the display,
others with flashing signs or the leds assembled on the control
unit.
Summary of Contents for AYROS
Page 30: ...ITALIANO 28 ...
Page 32: ...ITALIANO 30 ...
Page 60: ...ENGLISH 58 ...
Page 62: ...ENGLISH 60 ...
Page 90: ...FRANÇAIS 88 ...
Page 92: ...FRANÇAIS 90 ...
Page 120: ...ESPAÑOL 118 ...
Page 122: ...ESPAÑOL 120 ...
Page 150: ... 148 PORTUGUÊS ...
Page 152: ... 150 PORTUGUÊS ...
Page 180: ...DEUTSCH 178 ...
Page 182: ...DEUTSCH 180 ...
Page 210: ...NEDERLANDS 208 ...
Page 212: ...NEDERLANDS 210 ...
Page 240: ... 238 POLSKI ...
Page 242: ...POLSKI ...
Page 243: ......