ENGLISH
- 60 -
DISPLAYING
DESCRIPTION
SOLUTION
The display shows
Err3
When a start command is given the gate
won’t open.
It means that the photocell test failed.
1.
Be sure that no obstacle interrupted the photocell
beam when the Start command was given.
2.
Be sure that photocells, as enabled by their relevant
menus, have been installed actually.
3.
If you have photocells 2, be sure that
Fot2
menu
item is on
CF.Ch
.
4.
Be sure that photocells are powered and working:
interrupt the ray and check that the photocell segment
on the display changes position.
5.
Ensure the photocells are connected correctly, as
shown in the chapter 5.5
The display shows
Err4
When a Start command is given and the
gate does not open (or does a partial
opening).
It means that the limit switche has not been
released or that both limit switches are
active.
Make sure that the limit switches are correctly connected
and the gate, opening, let the limit switch open.
If the limit switches are not used set the parameter
FC.En
=
no
The display shows
Err5
When a start command is given the gate
won’t open.
It means that the test of the safety edges
failed.
1.
Make sure that the menu relative to the test of the
facets for cables (
Co.tE
) is configured correctly.
2.
Make sure that the safety edges enabled by menu are
actually installed.
3.
Check the safety edges are correctly connected as
indicated in chapter 5.6.
The display shows
Err8
When executing a self-learning function the
control is refused.
It means that the setting of the control
unit is not compatible with the requested
function.
1. Check the Start inputs are enabled in standard mode
(
Strt
menu set on
StAn
).
2. Check the ADI interface is disabled
(
i.Adi
menu set to
no
).
The display shows
Err9
It means that programming was locked by
means of the programming lock key CL1+
(code 161213).
To change the settings it is necessary to insert in the
connector of the ADI interface the same key used to
activate the programming lock, and unlock the device.
The display shows
Er10
When a start command is given the gate
won’t open.
This means that the ADI module function
test failed.
1.
Check the ADI module is correctly inserted
2.
Check the ADI module is not damaged and working
properly