ENGLISH
GATE DELAY DURING OPENING
In order to avoid any collision of the gate during the
opening phase, the time of delay should be
introduced r.AP, which is adjustable from 0 to 120
seconds (±0,5) .In such a case the opening time of
gate 2 is delayed in comparison to the gate 1.
GATE DELAY DURING CLOSING
In order to avoid the colliding of gate's during the
closing the time of delay should de introduced r.Ch,
which is adjustable from 0 to 120 seconds (±0,5).In
such a case the closing time of gate1 is delayed in
comparison to the gate2.
LOCK TIME
When the gate starts the opening phase, the control
unit must excite the electro lock in order to hook it
out and enable the opening of the gate. The time
t.SEr determines the duration of excitation, and is
adjustable from 0 to 120 seconds (±0,5).
LOCK ADVANCE TIME
This menu permits to anticipate the excitation of the
lock on a set time from 0 to t.SEr (with a scanning
of ±0,5). During the advance locking time the gate
does not move so to always guarantee the
unhooking of the electrical lock.
31