12 - LOADING THE DEFAULT PARAMETERS
If necessary, it is possible to restore all parameters to their standard or default values (see the final summary table).
m
PLEASE NOTE: This procedure results in the loss of all customised parameters, and hence it has been included outside the
configuration menu, in order to minimise the likelihood of it being run in error.
1.
Press and hold the
OK
key until the display shows
-dEF
2.
Release the
OK
key: the display shows
ESC
(only press the
OK
key if it is desired to exit this menu)
3.
Press the
i
key: the display shows
dEF
.
4.
Press the
OK
key: the display shows
no
5.
Press the
i
key: the display shows
Si
6.
Press the
OK
key: all parameters are overwritten with their default values (see Chapter 17.2), the control units exits programming
mode and the display shows the control panel.
13 - INSTALLATION MENÙ (SEt)
This menu allows to move the door as required during installation.
The automatic self-teaching procedure allows to store the positions of the limit switch sensors and of the opening and closing slow-down
starting points.
The manual handling procedure allows to control the door in hold to run mode in special cases such as during installation/maintenance or
a malfunction of the photocells or edges
m
CAUTION: ATTENTION: before proceeding, make sure to position the mechanical stops and the limit sensors correctly.
1.
Press and hold the
OK
key until the display shows
-SEt
2.
Release the
OK
key: the display shows
ESC
(only press the
OK
key if it is desired to exit this menu)
3.
Use the keys
h
and
i
to select the menu
Mov
to activate manual handling or
APPr
to start the automatic learning procedure
of the run limits.
4.
Press
OK
to start the selected procedure