SAFET
Y INFORMA
TION
4.1 Transportation
4.2 Preparation
4.4 Operation
4.3 Installation
• Transport the UPS system only in the original package to protect against shock and impact
• Condensation may occur if the UPS system is moved directly from a cold to warm environment. The UPS
system must be absolutely dry before being installed. Please allow at least two hours for the UPS system
to acclimate the environment.
• Do not install the UPS system near water or in moist environments.
• Do not install the UPS system where it would be exposed to direct sunlight or near a heater
• Do Not block ventilation holes in the UPS housing.
• Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket
outlet) during operations since this would cancel the protective earthing of the UPS system and of all
connected loads.
• The UPS system features its own, internal current source (batteries). The UPS output sockets or output
terminals block may be electrically live even if the UPS system is not connected to the building wiring
outlet.
• In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.
• Prevent fluids and other foreign objects from entering the UPS system.
• The EPO, RS-232 and USB circuits are IEC 60950-1 safety extra low voltage circuits by reinforced insulation
• Do not connect appliances or devices which can overload the UPS system (e.g. laser printers) to the UPS
output sockets
• Place cables in such a way that no one can step on or trip over them.
• Do not connect appliances such as hair dryers to UPS output sockets.
• Connect the UPS system only to an earthed shock proof outlet.
• Please use only the included VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer)
to connect the UPS system to the building wiring outlet (shockproof outlet).
• Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
• When installing the equipment, ensure that the sum of the leakage current of the UPS and the connected
devices does not exceed 3.5mA
• Temperature Rating - Units are considered acceptable for use in a maximum ambient temperature of
40°C (104°F)
• FOR PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall be easily
accessible.
• CAUTION: The unit is heavy. Lifting the unit requires at least two people
• Check if there is a protection devices against over current and short circuit in the upstream of the UPS
system. The recommended protection specification is 11A for 800VA~1100VA, 15A for 1.5 VA, 20A for LV
2KVA and 30A for 2.5~3KVA with a B or C trip curve.
Summary of Contents for UPS1RM2U1500
Page 86: ...www V7world com V5 20180523...