5. Disable and enable EPO function
This UPS is equipped with EPO function. Pin 1 and Pin2 are closed by default for normal UPS operation.
Note:
The EPO function logic can be set up via LCD setting. Please refer to program 16 in UPS setting for the details
1.5 Battery Replacement
Note:
This UPS is equipped with internal batteries and only a trained technician should replace the batteries.
Note:
When battery is disconnected, equipment is not protected from power outages.
Caution! – Adhere to all warnings, cautions, and notes before replacing batteries.
1
2
3
4
Remove front panel
Disconnect battery wires
Pull out the battery box by removing two screws
on the front panel
Remove the top cover of battery box and replace
the inside batteries
5
6
7
Remove the top cover of battery
box and replace the inside
batteries
After replacing the batteries,
put the battery box back to the
its original location and screw it
tightly
Put the front panel back on the unit
6. Turn on the UPS
Press the ON/Mute Button on the front panel for two seconds to power on the UPS.
Note:
The battery charges fully during the first five hours of normal operation. Do not expect full battery run
capability during this initial charge period
7. Install software (Optional for advanced users)
For optimal computer system protection, install UPS monitoring software to fully configure the UPS system. Please
follow steps below to download and install monitoring software.
1. Go to the website
http://www.V7-world.com/downloads
2. Select ViewPower software for your operating system to download the software.
3. Follow the on-screen instructions to install the software.