38
… 8 Commissioning
… Mechanical mounting checks
Moving to end positions after completion of automatic
adjustment
Process display
1. Use
to switch to the Operating Mode menu.
Operating mode
Auto Adjust
O
Adaptive
O
Control
O
Manual SP
O
Manual Sensor
Configuration
Back
OK
2. Use
or
to select the ‘Manual Sensor’ operating mode.
3.
Use
and
to move to the relevant end positions.
-45.0
Pos. Ang.
°
Check the end positions. The angle of rotation is displayed in
degrees.
Recommended range:
•
between
Æ
30 to 30° for linear actuator
•
between
Æ
45 to 45° for rotary actuator
Moving to end positions with a new device
Process display
1. Use
and
to move to the relevant end positions.
-45.0
Pos. Ang.
°
Check the end positions. The angle of rotation is displayed in
degrees.
Recommended range:
•
between
Æ
30 and 30° for linear actuator
•
between
Æ
45 and 45° for rotary actuator
Auto Adjust must then be performed.
See
Start automatic adjustment
on page 43.