60
… 9 Operation
… Parameter descriptions
Menu / parameter
Value range
Description
Controller (continued)
KP Up
1.0 to 400.0
Use this parameter to adjust the KP value for the
up
positioning direction (towards 100 %).
The KP value is the gain of the controller. The control speed and stability are influenced by the KP value.
With higher KP values, the control speed increases.
To compensate for existing dissymmetries in the controlled system, the KP value should be set
separately for both positioning directions (up / down). For most actuators, satisfactory control
behavior is achieved with a KP value between 2.0 and 10.0.
Note
The control precision is not affected by the KP value.
KP Down
1.0 to 400.0
Use this parameter to adjust the KP value for the
down
positioning direction (towards 0 %).
The KP value is the gain of the controller. The control speed and stability are influenced by the KP value.
With higher KP values, the control speed increases.
To compensate for existing dissymmetries in the controlled system, the KP value should be set
separately for both positioning directions (up / down). For most actuators, satisfactory control
behavior is achieved with a KP value between 2.0 and 10.0.
Note
The control precision is not affected by the KP value.
TV Up
10 to 800 ms
Use this parameter to adjust the KP value for the
up
positioning direction (towards 100 %).
The TV value is the derivative time of the controller.
The control speed and stability are affected by the TV value in such a way that it counteracts the KP
value dynamically. The control speed decreases as the TV value increases.
To compensate for existing dissymmetries in the controlled system, the TV value should be configured
separately for both positioning directions (up / down).
TV Down
10 to 800 ms
Use this parameter to adjust the TV value for the
down
positioning direction (towards 0 %).
The TV value is the derivative time of the controller.
The control speed and stability are affected by the TV value in such a way that it counteracts the KP
value dynamically. The control speed decreases as the TV value increases.
To compensate for existing dissymmetries in the controlled system, the TV value should be configured
separately for both positioning directions (up / down).
Summary of Contents for D500
Page 82: ...82 17 Appendix Control Drawing 901305...
Page 83: ...83...
Page 84: ...84 17 Appendix Control Drawing 901305...
Page 85: ...85...
Page 86: ...86 17 Appendix Control Drawing 901305...
Page 87: ...87...