Priority Fault message
Possible cause
Troubleshooting the Instrument
F
C
S
M
Group
44
67
Binary input active
Digital input activated by the
user
Deactivate the digital input
X
Special
Requirements
45
68
Switchpoint 1 exceeded
Valve has passed limit 1 position Depends on application
X
Process
46
69
Switchpoint 2 exceeded
Valve has passed limit 2 position Depends on application
X
Process
47
82
Analog output supply fault No power supply on analog
output
Check the supply power
X
Special
Requirements
48 81 Pressure
measurement
defect
‘Print option’ optional module
defective
Replace ‘Print option’ optional
module
X
Electronics
202
Extern access
Communication with the device
is performed via HART
Depends on application
X
Configuration
203
All locked
Local operation is locked
Activate the digital input
X
Configuration
204
Conf. Locked
Configuration is locked
Activate the digital input
X
Configuration
205
Panel
locked
Input
locked
X
Configuration
206
Simulation
Simulation
active
Terminate
simulation.
X
Configuration
207
Squawk*
‘Find device’ activated
Deactivate function in DTM or EDD
X
Configuration
* Function available only via HART®7