commissioning
vacon
•
31
24-hour support (0)201 212 575 • Email: vacon@vacon.com
4
7
Perform test run
without motor
. Perform either Test A or Test B:
A)
Control from the I / O terminals:
• Turn the Start / Stop switch to ON position.
• Change the frequency reference (potentiometer).
• Check the Monitoring Menu and make sure that the value of Output fre-
quency changes according to the change of frequency reference.
• Turn the Start / Stop switch to OFF position.
B)
Control from the keypad:
• Select the keypad as the control place with par 2.1. You can also move to
keypad control by pressing Loc / Rem button or select Local control with
par 2.5.
• Push the Start button on the keypad.
• Check the Monitoring Menu and make sure that the value of Output fre-
quency. changes according to the change of frequency reference.
• Push the Stop button on the keypad.
8
Run the no-load tests without the motor being connected to the process, if possi-
ble. If this is impossible, secure the safety of each test prior to running it. Inform
your co-workers of the tests.
• Switch off the supply voltage and wait up until the drive has stopped.
• Connect the motor cable to the motor and to the motor cable terminals of
the frequency converter.
• See to that all Start / Stop switches are in Stop positions.
• Switch the mains ON.
• Repeat test 7A or 7B.
9
Perform an identification run (see par. 1.18), especially if the application requires
a high startup torque or a high torque with low speed.
10
Connect the motor to the process (if the no-load test was running without the
motor being connected).
• Before running the tests, make sure that this can be done safely.
• Inform your co-workers of the tests.
• Repeat test 7A or 7B.
Summary of Contents for 10
Page 1: ......
Page 17: ...14 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 3P 230 V POWER LOSS ...
Page 18: ...installation vacon 15 24 hour support 0 201 212 575 Email vacon vacon com 3 ...
Page 19: ...16 vacon installation Tel 358 0 201 2121 Fax 358 0 201 212205 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 20: ...installation vacon 17 24 hour support 0 201 212 575 Email vacon vacon com 3 ...