Installation
vacon • 15
24-hour s358 (0)201 212 575 • Email: vacon@vacon.com
4
4.2
Installation in Vacon® 100 X
The AC drive can be connected to fieldbus either through RS485 or Ethernet. The connection for
RS485 is on the standard I/O terminals (A and B) and the connection for Ethernet is left to the control
terminals.
Figure 3.
4.2.1
Prepare for use through Ethernet
For more detailed information, see the user’s manual of the fieldbus you are using.
1
Connect the Ethernet cable (see specification in Chapter 3.2) to its terminal and
run the cable through the conduit plate.
2
Remount the powerhead.
NOTE:
When planning the cable runs, remember to keep the distance between
the Ethernet cable and the motor cable at a minimum of 30 cm.