Programming
vacon • 23
24-hour s358 (0)201 212 575 • Email: vacon@vacon.com
5
5.3.2
Modbus RTU monitoring values
P5.X.3.2.1
Fieldbus Protocol Status
tells the status of the protocol.
Table 9. FB protocol statuses
P5.X.3.2.2
The
Communication status
shows how many error and how many good messages the AC drive has
received. The Communication status includes a common error counter that counts CRC and parity
errors and a counter for good messages.
Only messages to the current slave in use are counted in the good messages.
Table 10.
P5.X.3.2.3
This value counts error situations.The function code received in the query refers to an unallowed
action for the server (or slave). This corresponds to Modbus fault code 01
h
.
P5.X.3.2.4
This value counts error situations. The data address received in the query refers to an unallowed
address for the server (or slave). This corresponds to Modbus fault code 02
h
.
P5.X.3.2.5
This value counts error situations. A value contained in the query data field refers to an unallowed
value for server (or slave). This corresponds to Modbus fault code 03
h
.
P5.X.3.2.6
This value counts error situations. The server (or slave) is engaged in processing a long–duration
program command. The client (or master) should retransmit the message later when the server (or
slave) is free. This corresponds to Modbus fault code 06
h
.
P5.X.3.2.7
This value counts error situations.The server (or slave) attempted to read record file but detected
a parity error in the memory.This corresponds to Modbus fault code 08
h
.
INITIALIZING
Protocol is starting up
STOPPED
Protocol is timeouted or not used
OPERATIONAL
Protocol is running
FAULTED
Major fault in protocol, requires restarting.
If fault remains contact fieldbus@vacon.com
Good messages
0…999
Number of messages received with-
out errors
Bad Frames
0…99
Number of messages received with
errors