Technical data
vacon • 67
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
7.3
VACON
®
100 X - technical data
Table 33. VACON
®
100 X technical data.
Mains connection
Input voltage U
in
3AC 208…240V
3AC 380...480V
3AC 380...500V
Input voltage
tolerance
-15%...+10% continuously
Input frequency
50/60 Hz
Protection class
I
Input frequency
tolerance
47.5...66 Hz
Connection to mains
Once per minute or less
Starting delay
<7 s
Supply network
TN- and IT-network (cannot be used with corner
earthed network)
Short-circuit current
Max. short-circuit current has to be < 100kA
DC connection
Input Voltage U
DC
:
234 … 400VDC
436 … 800VDC
Input voltage tolerance: No tolerance permissible,
0%
Motor connection
Output voltage
3AC 0... U
in
Rated output current
I
N
: Ambient temperature max. +40°C. See Table ,
Table 29 and Table 30.
Overload output
current
1.5 x I
N
(1 min/10 min);
1.1 x I
N
(1 min/10 min) only for MM6 0072.
See Table , Table 29 and Table 30.
Starting output current
I
S
for 2 s every 20 s.
See Table , Table 29 and Table 30.
Output frequency
0…320 Hz (standard)
Frequency resolution
0.01 Hz
Protection class
I
Motor characteristics
AC squirrel cage motors
Permanent magnet motors
Cable type
Screened motor cable
Cable maximum length
(full EMC compliance)
C2: 5m