46
•
vacon
monitoring & parameters
5
5.20 System parameters
Code
Parameter
Min
Max Default
ID
Note
Software information (MENU PAR -> V1)
V1.1
API SW ID
2314
V1.2
API SW version
835
V1.3
Power SW ID
2315
V1.4
Power SW version
834
V1.5
Application ID
837
V1.6
Application revision
838
V1.7
System load
839
When no field bus Option Board or no OPT-BH Board has been installed, the Modbus comm.
parameters are as follows
V2.1
Communication status
808
Status of Modbus
communication.
Format: xx.yyy
where xx = 0 - 64
(Number of error
messages)
yyy = 0 - 999
(Number of good
messages)
P2.2
Fieldbus protocol
0
1
0
809
0
= Not used
1
= Modbus used
P2.3
Slave address
1
255
1
810
P2.4
Baud rate
0
8
5
811
0
= 300
1
= 600
2
= 1200
3
= 2400
4
= 4800
5
= 9600
6
= 19200
7
= 38400
8
= 57600
Table 23: System parameters