general data
vacon
•
55
7
Vacon 20 power ratings
*The maximum ambient operating temperature of this drive is +40°C !
Mains voltage 208 - 240 V, 50 / 60 Hz, 1~ series
Fre-
quency
converter
type
Rated loadability
Motor shaft
power
Nominal
input
current
Mechanical
size
Weight
(kg)
100% contin.
current I
N
[A]
150% over-
load current
[A]
P
[HP]
P
[KW]
[A]
0001
1.7
2.6
0.33
0.25
4.2
MI1
0.55
0002
2.4
3.6
0.5
0.37
5.7
MI1
0.55
0003
2.8
4.2
0.75
0.55
6.6
MI1
0.55
0004
3.7
5.6
1
0.75
8.3
MI2
0.7
0005
4.8
7.2
1.5
1.1
11.2
MI2 0.7
0007
7
10.5
2
1.5
14.1
MI2
0.7
0009*
9.6
14.4
3
2.2
22.1
MI3
0.99
Table 25: Vacon 20 power ratings, 208 - 240 V
* The maximum ambient operating temperature of this drive is 40 °C!
Mains voltage 208 - 240 V, 50 / 60 Hz, 3~ series
Fre-
quency
converter
type
Rated loadability
Motor shaft
power
Nominal
input
current
Mechanical
size
Weight
(kg)
100% contin.
current I
N
[A]
150% over-
load current
[A]
P
[HP]
P
[KW]
[A]
0001
1.7
2.6
0.33
0.25
2.7
MI1
0.55
0002
2.4
3.6
0.5
0.37
3.5
MI1
0.55
0003
2.8
4.2
0.75
0.55
3.8
MI1
0.55
0004
3.7
5.6
1
0.75
4.3
MI2
0.7
0005
4.8
7.2
1.5
1.1
6.8
MI2 0.7
0007*
7
10.5
2
1.5
8.4
MI2
0.7
0011*
11
16.5
3
2.2
13.4
MI3
0.99
0012
12.5
18.8
4
3
14.2
MI4
9
0017
17.5
26.3
5
4
20.6
MI4
9
0025
25
37.5
7.5
5.5
30.3
MI4
9
0031
31
46.5
10
7.5
36.6
MI5
11
0038
38
57
15
11
44.6
MI5
11
Table 26: Vacon 20 power ratings, 208 - 240 V, 3~