monitoring & parameters
vacon
•
25
24-hour s358 (0)201 212 575 • Email: vacon@vacon.com
5
P3.4
Preset speed 0
P3.1
P3.2
Hz
5.00
180
Preset speed 0 is used
as frequency reference
when P3.3 = 1
P3.5
Preset speed 1
P3.1
P3.2
Hz
10.00
105
Activated by digital
inputs
P3.6
Preset speed 2
P3.1
P3.2
Hz
15.00
106
Activated by digital
inputs
P3.7
Preset speed 3
P3.1
P3.2
Hz
20.00
126
Activated by digital
inputs
Acceleration time
1
0.1
3000.0
s
3.0
103
Acceleration time from 0
Hz to maximum fre-
quency.
Deceleration time
1
0.1
3000.0
s
3.0
104
Deceleration time from
maximum frequency to 0
Hz.
P6.1
AI1 Signal range
0
1
0
379
0
= 0 - 100%
1
= 20% - 100%
20% is the same as 2 V
minimum signal level.
P6.5
AI2 Signal range
0
1
0
390
0
= 0 - 100%
1
= 20% - 100%
20% is the same as 2 V
or 4 mA minimum signal
level.
Automatic reset
0
1
0
731
0
= Disable
1
= Enable
P17.2
Parameter con-
ceal
0
1
1
115
0
= All parameters visi-
ble
1
= Only quick setup
parameter group visible
Code
Parameter
Min
Max
Unit
Default
ID
Note
Table 2: Quick setup parameters
P4.2
P4.3
P14.1