10. Controlling the motor from the front
panel
Vacon CX/CXL/CXS can have controls from
the I/O terminals or from the front panel. The
active control source can be changed with the
programmable push button b2 (see Chapter
6.). The motor can be started, stopped and
direction of rotation can be changed from the
active control source.
10.1 Control source change from I/O
terminals to front panel
After changing the control source the motor is
stopped. The direction of rotation remains the
same as with I/O control.
If the Start button is pushed at the same time
as the programmable push button b2, the Run-
state, direction of rotation and reference value
will be copied from the I/O terminals to the front
panel.
10.2
Control source change from panel
to I/O terminals
After changing the control source, the I/O
terminals determine the run-state, direction of
rotation and reference value.
If motor potentiometer is used in the
application, the panel reference value can be
copied for a value of motor potentiometer
reference by pushing the start button at the
same time as the programmable push button
b2. Motor potentiometer function mode must
be "resetting at stop state" (Local/Remote
Application: param. 1. 5 =4, Multi-purpose
Application : param. 1. 5 = 9).