5.2.2 FieldBus Monitoring values
V1.25.1
FB Control Word
ID1160
Control word used in bypass mode. See P2.13.22 and option board ByPass.
More details in Chapter 9 Status and Control Word in detail.
Bit
Description
Value = 0
Value = 1
b0
OFF
ON, Reset after Fault or b1 and b2
b1
Emergency stop by coast
ON, On normal operation: Keep TRUE
b2
Emergency stop by ramp
ON, On normal operation: Keep TRUE
b3
STOP REQUEST
RUN REQUST
b4
Force ramp to Zero
Enable Ramp,
b5
Freeze Ramp
Enable Ramp,
b6
Force Ref to Zero
Enable Ramp,
b7
No Action
FAULT RESET (0 -> 1)
b8
No Action
Inching 1
b9
No Action
Inching 2
b10
Disable Profibus control
Enable Profibus control
b11
Fieldbus DIN1=OFF
Fieldbus DIN1=ON (Watchdog pulse)
b12
Fieldbus DIN2=OFF
Fieldbus DIN2=ON
b13
Fieldbus DIN3=OFF
Fieldbus DIN3=ON
b14
Fieldbus DIN4=OFF
Fieldbus DIN4=ON
b15
No Action
No Action
V1.26.2
FB Speed Reference
ID875
FB Speed Reference from the fieldbus
V1.25.2
FB Status Word
ID65
ProfiDrive type status word. Not the same as used by Profibus board in
ProfiDrive mode. Needs to be selected with P2.14.19 GSW to be used. See
details in Chapter 9 Status and Control Word in detail.
Bit
Description
Value = 0
Value = 1
b0
Not ready to switch on
Ready to switch on
b1
Not ready to operate
Ready to operate
b2
Not Running
Running
b3
No Fault
Fault
b4
Coast stop Active
Coast stop not active
b5
Quick stop active
Quick stop not active
b6
Switch not inhibited
Switch on inhibit
b7
No Warning
Warning
b8
Speed error
Speed At Reference
b9
No FB Control request
FB Control Active
b10
Fout < Fmax
Fout > Fmax
b11
not used
not used
b12
not used
not used
b13
not used
not used
b14
not used
not used
b15
Fieldbus DIN1=OFF
Fieldbus DIN1=ON (Watchdog pulse)