3
vacon • 24
CANopen protocol description
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
3.7.9
0X1017 - Producer Heartbeat Time
Heartbeat producer object consists of the time in milliseconds (ms) that it takes to transmit the
heartbeat message into the network. If the value is zero, the heartbeat is not used.
3.7.10
0X1018 - Identify Object
The object gives information about the option board
3.7.11
0X1019 - Synchronous counter overflow value
The synchronous counter overflow value defines whether a counter is mapped into the SYNC mes-
sage, as well as the highest value the counter can reach. 0 disables the sync counter.
Table 42: 0x1017 Producer heartbeat time
Index
Sub-index
Value
Name
Data type
Access
0x1017
-
0x0000
Producer
heartbeat time
UNSIGNED16
r/w
Table 43: Heartbeat message
CAN ID
LENGTH
DATA0
0x700 + node
0x1
Node state
Table 44: 0x1018 Identify object
Index
Sub-index
Value
Name
Data type
Access
0x1018
0
0x04
Number of entries
UNSIGNED8
ro
1
0x90
Vendor ID
UNSIGNED32
ro
2
-
Product code
UNSIGNED32
ro
3
-
Revision number
UNSIGNED32
ro
4
-
Serial number
UNSIGNED32
ro
Table 45: 0x1019 Synchronous counter
Index
Sub-index
Value
Name
Data type
Access
0x1019
-
0x00
Synchronous
counter
UNSIGNED8
r/w
Summary of Contents for CANopen OPTE6
Page 1: ...vacon ac drives canopen option board opte6 user manual ...
Page 2: ......