5
vacon • 34
OPTE6 layout and connections
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Figure 11. CAN shield grounding option
A = CAN connector pin 3 (shield) connected to the drive chassis with a high-impedance RC circuit.
Recommended option when equipotential bonding is poor.
B = CAN connector pin 3 (shield) connected directly into the drive chassis. Recommended option
when equipotential bonding is good. (Factory default setting)
C = CAN connector pin 3 is not connected.
3
1
2
3
2
1
1
2
3
A
B
C