Commissioning
vacon • 53
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
7
7.
C
OMMISSIONING
This chapter describes how to commission the OPTE6 board for use. For instructions on how to set-
up the AC drive to be controlled over fieldbus, refer to Chapter 11 Appendix B - Fieldbus parame-
trization.
7.1
OPTE6 panel parameters
Different number of panel parameters are visible depending on the used AC drive and version. VA-
CON
®
20 family option board parameters are under SYS menu.
* From version V26 (INDUSTRIAL) and V18 (FLOW)
Table 53. OPTE6 board basic parameters
#
Panel code
Parameter
Min
Max
Default
Description
VACON
®
100
family
VACON
®
20
family
1
P5.x.3.1
P2.2
Node ID
1
127
1
Network-wide unique identifier
for each CANopen device
2
P5.x.3.2
P2.3
Baud Rate
3
8
5
Data signalling rate. Should be
the same on each node in the
same bus. See Table 54
3
P5.x.3.3
P2.4
Operate Mode
1
4
1
Selection between OPTE6 operate
modes. See Table 55
5
P5.x.3.4*
-
Comm.
Timeout
0
65535
1
Timeout in seconds for CAN
communication faults (PASSIVE,
BUS-OFF)
6
P5.x.3.5*
-
Restore from
Set
0
1
0
0'1 All CANopen parameters are
reset to default values based on
Operate Mode.
7
P5.x.3.6*
-
Mode
0
1
0
Set OPTE6 mode. See Table 56
Table 54. OPTE6 Baud Rate settings
Value
Bit rate
1
10 kbps (not supported)
2
20 kbps (not supported)
3
50 kbps
4
100 kbps
5
125 kbps
6
250 kbps
7
500 kbps
8
1000 kbps
Table 55. OPTE6 Operate Mode settings
Value
Name
Description
1
Drive Profile
CiA-402 drive profile, velocity mode active
Summary of Contents for CANopen OPTE6