CANopen option board interface
vacon • 73
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8
8.2.3.2
Transmit PDO configuration
Configuration of the transmit PDO configuration is the following, when the CiA-402 vl parameter set
is restored:
Table 73. Receive PDO Communication Parameter 1
Index
Sub-index
Value
Name
Data type
Access
0x1400
0
5
Highest sub-index
UNSIGNED8
ro
1
0x200 + Node
ID
COB-ID
UNSIGNED32
r/w
2
0xFE
Transmission type
UNSIGNED32
r/w
3
100
Inhibit time
UNSIGNED16
r/w
4
-
Reserved
UNSIGNED8
ro
5
0
Event timer
UNSIGNED16
r/w
Table 74. Receive PDO Communication Parameter 2
Index
Sub-index
Value
Name
Data type
Access
0x1401
0
5
Highest sub-index
UNSIGNED8
ro
1
0x80
Node ID
COB-ID
UNSIGNED32
r/w
2
0xFE
Transmission type
UNSIGNED32
r/w
3
1000
Inhibit time
UNSIGNED16
r/w
4
-
Reserved
UNSIGNED8
ro
5
0
Event timer
UNSIGNED16
r/w
Table 75. Receive PDO Communication Parameter 3
Index
Sub-index
Value
Name
Data type
Access
0x1402
0
5
Highest sub-index
UNSIGNED8
ro
1
0x80
Node ID
COB-ID
UNSIGNED32
r/w
2
0xFE
Transmission type
UNSIGNED32
r/w
3
1000
Inhibit time
UNSIGNED16
r/w
4
-
Reserved
UNSIGNED8
ro
5
0
Event timer
UNSIGNED16
r/w
Table 76. Transmit PDO Mapping Parameter 1
Index
Sub-index
Value
Name
Data type
Access
0x1A00
0
2
Number of entries
UNSIGNED8
r/w
1
0x60410010
Statusword
UNSIGNED32
r/w
2
0x60440010
vl Velocity Actual Value
UNSIGNED32
r/w
Summary of Contents for CANopen OPTE6
Page 1: ...vacon ac drives canopen option board opte6 user manual ...