8
vacon • 76
CANopen option board interface
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
8.3.1.1
Receive PDO configuration
Configuration of the receive PDO configuration is the following, when the Bypass parameter set is
restored:
* Data inside 'FB PD in' varies according to the drive application and used settings.
* Data inside 'FB PD in' varies according to the drive application and used settings.
Table 83. Overview of Transmit PDO configuration in Bypass mode
Object
COB-ID
Size
DATA0
DATA1
DATA2
DATA3
DATA4
DATA5
DATA6
DATA7
TPDO1
0x180 +
Node ID
6
0x2001,1
FB Status Word
0x2001,2
FB General
Status Word
0x2001,3
FB Actual Speed
Not used
TPDO2
0x280 +
Node ID
8
0x2001,4
FB PD out 1
0x2001,5
FB PD out 2
0x2001,6
FB PD out 3
0x2001,7
FB PD out 4
TPDO3
0x380 +
Node ID
8
0x2001,8
FB PD out 5
0x2001,9
FB PD out 6
0x2001,A
FB PD out 7
0x2001,B
FB PD out 8
Table 84. Receive PDO Mapping Parameter 1
Index
Sub-index
Value
Name
Data type
Access
0x1600
0
3
Number of entries
UNSIGNED8
r/w
1
0x20000110
FB Control Word
UNSIGNED32
r/w
2
0x20000210
FB General Control
Word
UNSIGNED32
r/w
3
0x20000310
FB Speed Reference
UNSIGNED32
r/w
Table 85. Receive PDO Mapping Parameter 2
Index
Sub-index
Value
Name
Data type
Access
0x1601
0
4
Number of entries
UNSIGNED8
r/w
1
0x20000410
FB PD in 1*
UNSIGNED32
r/w
2
0x20000510
FB PD in 2*
UNSIGNED32
r/w
3
0x20000610
FB PD in 3*
UNSIGNED32
r/w
4
0x20000710
FB PD in 4*
UNSIGNED32
r/w
Table 86. Receive PDO Mapping Parameter 3
Index
Sub-index
Value
Name
Data type
Access
0x1602
0
4
Number of entries
UNSIGNED8
r/w
1
0x20000810
FB PD in 5*
UNSIGNED32
r/w
2
0x20000910
FB PD in 6*
UNSIGNED32
r/w
3
0x20000A10
FB PD in 7*
UNSIGNED32
r/w
4
0x20000B10
FB PD in 8*
UNSIGNED32
r/w