Appendix B - Fieldbus parametrization
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
11.1.1
Controlling fieldbus parameter
In VACON
®
100 family products, if multiple fieldbus options or protocols are active at once, use the
"Controlling Fieldbus"-parameter to select the instance from which the process data is sent to the
drive application. This parameter is located under I/O and Hardware / Fieldbus General (5.13.1).
By default, the setting is in "Automatic" and the functionality (when receiving process data from
multiple sources) is application dependent.
For example, if a fieldbus option board has been installed to slot E and it is used with to control the
drive, user can select "Slot E" as value for this parameter. Now only the process data from the option
board in slot E is forwarded to the application. All other fieldbuses will still receive process data out.
With this setting it is possible to prevent that the monitoring fieldbuses accidentally write process
data in.
Table 122. Fieldbus parametrization for VACON
®
20X (multipurpose application)
Parameter name
ID
Value
Default
Panel Tree
Motor control mode
600
0 = Frequency
1 = Speed
0
P8.1
Control place selection
125
2 = Fieldbus
0
P1.11
Frequency ref. sel.
1819
5 = Fieldbus
0
P1.12
Table 123. Fieldbus parametrization for VACON
®
NXP (multipurpose application)
Parameter name
ID
Value
Default
Panel Tree
Motor control mode
600
0 = Frequency
1 = Speed
2 = Torque
0
P2.6.1
Control place selection
125
3 = Fieldbus
1
P3.1
Frequency ref. sel.
122
9 = Fieldbus
3
P2.1.13
Table 124.
Value name
Value
Description
Automatic
1
Process data from all sources is forwarwed to application
Slot D
2
Only process data from slot D is forward to application.
Value is visible only, if option board is installed to slot D.
Slot E
3
Only process data from slot E is forward to application.
Value is visible only, if option board is installed to slot E.
RS485
4
Only process data from VACON
®
100 family internal RS 485
protocol is forwarded to application
PROFINET IO
5
Only process data from VACON
®
100 family internal PROFI-
NET IO protocol is forwarded to application
EtherNet/IP
6
Only process data from VACON
®
100 family internal Ether-
Net/IP protocol is forwarded to application