CANopen option board OPTE6 - technical data
vacon • 27
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
4
4.
CAN
OPEN
OPTION
BOARD
OPTE6 -
TECHNICAL
DATA
4.1
General
4.2
CAN cable
The recommended cables for installations are 4 wires twisted and a shielded cable with an
impedance of 120 Ohm. The network topology is a 2-wire bus line that is terminated at both ends by
resistors representing the characteristic impedance of the bus line. The typical CAN cable
impedance is 120 Ohm, and so for the termination resistors of ~120 Ohm must be used. For long
networks a higher resistor value must be used (150-300 Ohm).
Table 50. Technical data of CANopen option board
CAN bus electrical
isolation
500 VDC
Ambient
temperature
As specified in drive specification (-10°C … 40°C)
Storing temperature
As specified in drive specification (-40°C … 70°C)
Humidity
0-95%, non-condensing, corrosive
Vibration and
electrical safety
EN 61800-5-1 (2007)
5… 15.8 Hz 1mm (peak)
15.8 ...150 Hz 1 G
Emission
C2 level, EN 61800-3 (2004)
Immunity
C2 level, EN 61800-3 (2004)
CAN Interface
Isolation
2500 V rms isolation with a less than
10-ns propagation delay
Protection
±8kV ESD IEC 61000-4-2 Contact
Discharge
±80V Fault Protection
greater than ±12V common Mode Range
Table 51. Bus parameter relation to cable length
Cable length
Max bit rate [kbit/s]
Max cable resistance
[m
Ω
/m]
0-40 m
1000
Max 70
100 m
500
<
60
500 m
100
<
40
1 km
50
<
26
Summary of Contents for CANopen OPTE6
Page 1: ...vacon ac drives canopen option board opte6 user manual ...
Page 2: ......