TROUBLESHOOTING
Service Manual M4 - M10
11.07.2002
Page
35
F15
Check parameter settings and make corrections
to match with requirements of application
F15 MOTOR STALLED
Check mechanical load of the application versus
rating of the motor and the drive
Combination of the rating for motor and drive do
not match with mechanical load
Clear fault memory
F15
Measure actual motor current and compare it to
value on monitoring page v3
Measured current =
Monitored current
Check the current measuring circuit according to
instructions on section 7.3.2.1. Replace
defective parts as recommended in spare part
lists
NO
YES
NO
YES