TROUBLESHOOTING
Service Manual M4 - M10
11.07.2002
Page
37
F17
Check settings of parameters and set values
according to requirements of application
F17 MOTOR UNDER LOAD
Measure motor current and compare result to
value on monitoring page v3
Check the current measuring circuit according to
instructions on section 7.3.2.1. Replace
defective parts as recommended in spare part
lists
Clear fault memory
(t) measured = (t)
monitored
NO
YES