Summary of Contents for CX100OPT

Page 1: ... O O T H C O N T R O L I O e x p a n d e r b o a r d i n s t a l l a t i o n m a n u a l Va c o n C X S r a n g e Subject to changes without notice V A C O N C X C X L C X S F R E Q U E N C Y C O N V E R T E R S ...

Page 2: ...vacon com CONTENTS 1 GENERAL 2 1 1 Vacon CX100OPT 2 1 2 Vacon CX101OPT 2 1 3 Vacon CX102OPT 2 1 4 Vacon CX103OPT 2 1 5 Vacon CX104OPT 3 1 6 Vacon fieldbus boards 3 2 SPECIFICATIONS 4 3 INSTALLATION 5 3 1 General 5 3 2 Installation 6 4 CONTROL CONNECTIONS 1 1 4 1 Vacon CX100OPT 11 4 2 Vacon CX101OPT 12 4 3 Vacon CX102OPT 13 4 4 Vacon CX103OPT 14 4 5 Vacon CX104OPT 15 ...

Page 3: ...ctor Control 1 2 Vacon CX101OPT The available I O can be increased by using the Vacon CX101OPT I O expander board 5 digital inputs standard signals relay output standard signal thermistor input can be directly connected to the motor thermistors to monitor the motor temperature Typical use thermistor input required 1 3 Vacon CX102OPT The available I O can be increased by using the Vacon CX102OPT I ...

Page 4: ...I O expander board encoder input Typical use Closed Loop Vector Control 1 6 Fieldbus boards Vacon fieldbus boards can be installed in the Vacon CXS range frequency converters as I O expander boards The needed information to install commission fieldbus boards can be found in the respective Vacon fieldbus manual Vacon CX 200OPT Interbus S Vacon CX 201OPT Modbus Vacon CX 202OPT Profibus DP Vacon CX 2...

Page 5: ...3 V Ri 330 Ω Table 2 1 Specifications All the control connections are not found on every I O expander board for specific information see Chapters 1 and 4 The control connections are isolated from the mains potential and the I O ground is connected to the frame of the inverter via a 1 MΩ resistor and 4 7 nF capacitor The control I O ground can be connected directly to the frame by changing the posi...

Page 6: ...0 I O expander board 11 check that the typecode is corresponds to your order I O interface board 12 10 pole data cable 13 4 pole power cable 14 screws for I O expander board 15 screws for I O interface board 16 Figure 3 1 I O expander board parts If the delivery does not match your order please contact the supplier immediately Only a competent electrician should carry out the electrical installati...

Page 7: ...ng to the I O expander board 11 If I O expander board CX101OPT or 103OPT is in use jumper must be in position A If I O expander board CX100OPT or 102OPT is in use jumper must be in position B If one of the following fielbus boards is in use CX200OPT CX201OPT CX202OPT or CX203OPT jumper must be in position C Positon D is not in use X5 X4 Make sure that the cable of the control panel cover is connec...

Page 8: ... correctly located push the arms of the protection foil under the control panel cover Fasten the I O repeater board and protection foil to the stand sleeve 7 with the screw X14 Install the control panel cover with 4 screws 6 8 Connect the power cable 4 to the I O repeater terminal X1 and communication cable 9 to the I O repeater terminal X3 Uncover carefully the shield of the communication cable m...

Page 9: ...9 Note the jumper can be connected in ON or OFF position see Vacon CX CXL CXS User s manual Chapter 6 2 2 13 If you have the option box with the I O expander 11 and I O interface boards 12 pre installed jump to section 17 Mount the I O expanderboard 11 and I O interface board 12 in the option box 10 with the screws 11 Connect data cable 13 between terminal X14 in the I O interface board 12 and ter...

Page 10: ...al for more specific information X8 16 If an encoder input closed loop control is to be used and the encoder works at a 5V level move three jumpers from terminal X5 to terminal X8 If the encoder works at 24V then terminal X8 should be left free Check the connections and make sure that there are no foreign objects inside the option box Before connecting the mains make sure that the cover of the opt...

Page 11: ...01 2121 Fax 358 201 212 205 Service 358 40 8371 150 E mail vacon vacon com http www vacon com Figure 3 2 Frequency converter and external I O expander box installation unit sizes M3 and M4B I O expander box can also be installed beside the frequency converter unit sizes M3 M4B and M5B ...

Page 12: ...Contact open no fault closing contact Contact closed fault 210 DIC2 Run disable Cont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 selected selection Contact closed time 2 selected 212 DIC4 Jogging speed selection Contact open no action Contact closed jogging speed 213 DIC5 Fault reset Contact open no action Contact closed fault res...

Page 13: ...ct closed fault 210 DIC2 Run disable Cont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 selected selection Contact closed time 2 selected 212 DIC4 Jogging speed selection Contact open no action Contact closed jogging speed 213 DIC5 Fault reset Contact open no action Contact closed fault reset 214 N C Not connected 215 N C Not connec...

Page 14: ...tor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 selected selection Contact closed time 2 selected 212 DIC4 Jogging speed selection Contact open no action Contact closed jogging speed 213 DIC5 Fault reset Contact open no action Contact closed fault reset 214 DI6A Pulse input A 215 DI6A differential input 216 DI7B Pulse input B 90 degrees phase shift c...

Page 15: ...V 209 DIC1 External fault Contact open no fault closing contact Contact closed fault 210 DIC2 Run disableCont open start of motor enabled Cont closed start of motor disabled 211 DIC3 Acceler Decel time Contact open time 1 selected selection Contact closed time 2 selected 212 DIC4 Jogging speed selection Contact open no action Contact closed jogging speed 213 DIC5 Fault reset Contact open no action...

Page 16: ...GND I O ground Ground for controls 206 24V Control voltage output 207 GND I O ground Ground for controls 214 DI6A Pulse input A 215 DI6A differential input 216 DI7B Pulse input B 217 DI7B differential input 218 DIR Encoder direction 219 DIV Encoder divider 1 1024 4 5 Vacon CX104OPT More information on the Vacon CX104OPT encoder option board you will find in a separate manual ud318 Ask your distrib...

Page 17: ...V ACONPLC P O Box 25 Runsorintie 7 FIN 65381 VAASA FINLAND Phone 358 201 2121 Fax 358 201 212 205 Service 358 40 8371 150 E mail vacon vacon com http www vacon com Distributor U D 00244C1 19 10 2000 ...