fault tracing
vacon • 87
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
9
Fault
code
Fault
Possible cause
Correcting measures
59
Follower
communication
SystemBus is broken between Master
and Follower.
Check option board parameters.
Check optical fibre cable.
60
Cooling
Coolant circulation on liquid-cooled
drive has failed.
Check reason for the failure on external
system.
61
Speed error
Motor speed is unequal to reference.
Check encoder connection.
PMS motor has exceeded the pull out
torque.
62
Run disable
Run enable signal is low.
Check reason for Run enable signal.
63
Emergency stop
Command for emergency stop received
from digital input or fieldbus.
New run command is accepted after
reset.
64
Input switch open
Drive input switch is open.
Check the main power switch of the
drive.
65
PT100 board 2
temp fault
Temperature limit values set for the
PT100 board parameters have been
exceeded.
More inputs are selected than actually
connected.
PT100 cable is broken.
Find the cause of temperature rise.
74
Follower fault
When using normal Master Follower
function this fault code is given if one or
more follower drives trip to fault.
Table 9
-
1. Fault codes