16 • vacon
modbus
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
5
5.
COMMISSIONING
READ FIRST CHAPTER 8 'COMMISSIONING' IN VACON NX USER'S MANUAL (Document nr. ud00701,
Note! You must select Fieldbus as the active control place, if you wish to control the frequency con-
verter through fieldbus. See Vacon NX User’s Manual, Chapter 7.3.3.1.
5.1
Fieldbus board parameters
The Vacon RS-485 board is commissioned with the control keypad by giving values to appropriate pa-
rameters in menu M7 (for locating the expander board menu see Vacon NX User's Manual, Chapter
7).
Expander board menu (M7)
The
Expander board menu
makes it possible for the user 1) to see what expander boards are con-
nected to the control board and 2) to reach and edit the parameters associated with the expander
board.
Enter the following menu level (G#) with the
Menu button right
. At this level, you can browse through
slots A to E with the
Browser buttons
to see what expander boards are connected. On the lowermost
line of the display you also see the number of parameter groups associated with the board.
If you still press the
Menu button right
once you will reach the parameter group level where there are
two groups: Editable parameters and Monitored values. A further press on the
Menu button right
takes you to either of these groups.
RS-485 parameters
To commission the RS-485 board, enter the level P7.5.1.# from the
Parameters
group (G7.5.1). Give
desired values to all RS-485 parameters (see Figure 11 and Table 5).
Figure 11. Changing the RS-485 board commissioning parameter values
Expander Board
G1
G5
READY
I/Oter m
NXOPTC5
READY
I/Oter m
G1
G2
Slave address
READY
I/Oter m
126
enter
CHANGE VALUE
CONFIRM CHANGE
Parameters
READY
I/Oter m
P1
P4
Slave address
READY
I/Oter m
126