28 • vacon
modbus
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
6
6.2.4.1
Status word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
-
-
-
-
-
UVFS
DDI
R
TCSPDL
FR
Z
ARE
F
W
FLT
DIR
RUN
RDY
Information about the status of the device and messages is indicated in the
Status word
. The
Status
word
is composed of 16 bits that have the following meanings:
Bit
Description
Value = 0
Value = 1
0
Not Ready
Ready
1
STOP
RUN
2
Clockwise
Counterclockwise
3
-
Faulted
4
-
Warning
5
Ref. frequency not reached
Ref. Frequency reached
6
-
Motor is running at zero speed
7
Flux Not Ready
Flux Ready
8
TC Speed Limit Active
TC Speed Limit Not Active
9
Detected Encoder Direction Clockwise
Encoder Direction Counterclockwise
10
UV Fast Stop Active
UV Fast Stop Not Active
11...15
Not In use
Not In use
Table 15. Status word bit descriptions
6.2.4.2
General status word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
I/O
PANEL
FB
-
-
-
-
-
-
-
-
-
-
-
-
Bit
Description
0...12
Not in use
13
Fieldbus control, (1 = FB control active)
14
Panel control, (1 = Panel control active)
15
I/O Control, (1 = I/O control active)
Table 16. General status word bit descriptions