40 • vacon
metasys n2
Tel.+358 (0)201 2121 • Fax +358 (0)201 212 205
7
APPENDIX 1
Process Data OUT (Slave to Master)
The Fieldbus Master can read the frequency converter’s actual values using process data variables.
Basic, Standard, Local/Remote Control, Multi-Step Speed Control, PID control and Pump and fan con-
trol
applications use process data as follows:
ID
Data
Value
Unit
Scale
2104
Process data OUT 1
Output Frequency
Hz
0,01 Hz
2105
Process data OUT 2
Motor Speed
rpm
1 rpm
2106
Process data OUT 3
Motor Current
A
0,1 A
2107
Process data OUT 4
Motor Torque
%
0,1 %
2108
Process data OUT 5
Motor Power
%
0,1 %
2109
Process data OUT 6
Motor Voltage
V
0,1 V
2110
Process data OUT 7
DC link voltage
V
1 V
2111
Process data OUT 8
Active Fault Code
-
-
Table 26. Process data OUT variables
The
Multipurpose Control application
has a selector parameter for every Process Data. The monitor-
ing values and drive parameters can be selected using the ID number (see NX All in One Application
Manual, Tables for monitoring values and parameters). Default selections are as in the table above.
Process Data IN (Master to Slave)
ControlWord, Reference and Process Data are used with All-inOne applications as follows:
Basic, Standard, Local/Remote Control and Multi-Step Speed Control applications
ID
Data
Value
Unit
Scale
2003
Reference
Speed Reference
%
0.01%
2001
ControlWord
Start/Stop Command
Fault reset Command
-
-
2004–2011
PD1 – PD8
Not used
-
-
Table 27.