10.3.2. NXS software information
10. 3. 2. 1. NXS00001V160
•
Fixed “Identification run” bug.
10. 3. 2. 2. NXS00001V161
•
Known feature: option board parameters are not shown on the display if the option
board data is old (EEPROM data is wrong). Board data has to be updated.
10. 3. 2. 3. NXS00001V162
•
Fixed problem for F32. It does not appear, even if the FAN feedback is missing.
•
Known feature: option board parameters are not shown on the display if the option
board data is old (EEPROM data is wrong). Board data has to be updated.
10. 3. 2. 4. NXS00001V163
•
A bug caused panel-task to load parameters from panel, when panel starts.
•
Option board BacNet :Autobaud added.
10. 3. 2. 5. NXS00001V164
•
NCDrive did not find correct info about downloaded VCN-packet when trying to
communicate with unit having version 163 NXS software. Communication possible
after generating VCN file by using the function generate database.
10. 3. 2. 6. NXS00001V165
Replaced version: NXS00001V163.VCN
System software version: 11.68.8069
Changes in system software:
•
Increased filtering time for calculated open loop motor power.
•
Changes to stall protection function. Earlier there had to be difference between
speed reference and actual speed (current controller active) and now this condition
is removed.
•
When control board is supplied by ex24 V and the unit is one of the 690 V
series, the overvoltage trip can occur when main power is disconnected from power
section. Corrected.
Changes in applications:
•
Displayed analogue input units are set to follow the parameter setting of option
board parameteres (V or mA).
•
Some parameters were possible to change even that parameter lock was set on.
Corrected.