Fault codes and software
24h on-call service phone: +358 (0)40 83 71 150
92
4
F8
Sys-
tem
faults
S7
1=Power
2=Power
1
3=Power
2
1=Board
Control of the
charging relay
do not set.
Appears in the
NXP units, which
includes control
board VB00561.
Failure appears if the
system has external
relays which have longer
delay time than the used
program has. Check
external connections.
S8
1=Power
2=Power
1
3=Power
2
1=Unit
2=U
phase
3=V
phase
4=W
phase
Driver board
without auxil-
iary voltage.
Failure appears
in the unit sizes
FR9-FR14. Sig-
nal: ASIC-TRIN.
1. Check the phases U,
V, W.
Check the ASIC board
(VB00451).
3. Check connections
and connectors of the
optical fibres.
F9
S1
1=Power
1=Unit
DC-voltage too
low in run-state.
S2
1=Power
2=Power
1
3=Power
2
1=Unit
S3
1=Power
1=Unit
UV Fast Stop
F10
S1
1=Power
2=Power
1
3=Power
2
1 = Unit
S2
1=Power
1=Unit
In regenerative
unit
F11
S1
1=Power
1=Unit
F12
S1
1=Power
2=Power
1
3=Power
2
1=Unit
TABLE 16.
System software fault codes
Code
Sub
code
Module
Sub
module
Explanation
Fault mode