5.3.1
CABLE AND FUSE SIZES FOR 208-240 V AND 380-500 V, FR4 TO FR9
Table 24: The cable and fuse sizes for Vacon
®
NXS and NXP
Frame
Type
I
L
[A]
Fuse
(gG/gL) [A]
Mains, motor
and brake
resistor cable
Cu [mm
2
]
Terminal cable size
Mains cable
terminal
[mm
2
]
Grounding
terminal
[mm
2
]
FR4
0003 2—0008 2
0003 5—0009 5
3–8
3–9
10
3*1.5+1.5
1–4
1–4
0011 2—0012 2
0012 5
11–12
12
16
3*2.5+2.5
1–4
1–4
FR5
0017 2
0016 5
17
16
20
3*4+4
1–10
1–10
0025 2
0022 5
25
22
25
3*6+6
1–10
1–10
0031 2
0031 5
31
31
35
3*10+10
1–10
1–10
FR6
0048 2
0038 5—0045 5
48
38–45
50
3*10+10
2.5–50 Cu
6–50 Al
2.5–35
0061 2
0061 5
61
63
3*16+16
2.5–50 Cu
6–50 Al
2.5–35
FR7
0075 2
0072 5
75
72
80
3*25+16
2.5–50 Cu
6–50 Al
6–70
0088 2
0087 5
88
87
100
3*35+16
2.5–50 Cu
6–50 Al
6–70
0114 2
0105 5
114
105
125
3*50+25
2.5–50 Cu
6–50 Al
6–70
POWER CABLING
VACON · 47
24-HOUR S358 (0)201 212 575 · EMAIL: VACON@VACON.COM
5