7.4
USING THE MONITORING MENU (M1)
You can monitor the actual values of the parameters and signals. You cannot change the
values in the Monitoring menu. To change the values of parameters, see Chapter 7.5 Using
the Parameter menu (M2).
The monitored signals have the indication V#.#. The values update each 0.3 seconds.
Table 40: Monitored signals
Index
Monitoring value
Unit
ID
Description
V1.1
Output frequency
Hz
1
The output frequency to the motor
V1.2
Frequency reference
Hz
25
The frequency reference to motor control
V1.3
Motor speed
rpm
2
The actual speed of the motor in rpm
V1.4
Motor current
A
3
Measured motor current
V1.5
Motor torque
%
4
The calculated shaft torque
V1.6
Motor power
%
5
The calculated motor shaft power in percentage
V1.7
Motor voltage
V
6
The output voltage to the motor
V1.8
DC link voltage
V
7
The measured voltage in the DC-link of the drive
V1.9
Unit temperature
°C
8
The heat sink temperature in Celsius or Fahren-
heit
V1.10
Motor temperature
%
9
The calculated motor temperature in percentage
of the nominal temperature. See All-in-One Appli-
cation Manual.
V1.11
Analogue input 1
V/mA
13
AI1 *
V1.12
Analogue input 2
V/mA
14
AI2 *
V1.13
DIN 1, 2, 3
15
Shows the status of the digital inputs 1-3
V1.14
DIN 4, 5, 6
16
Shows the status of the digital inputs 4-6
V1.15
DO1, RO1, RO2
17
Shows the status of the digital and relay outputs
1-3
V1.16
Analogue I
out
mA
26
AO1
V1.17
Multimonitoring
items
Displays 3 monitoring values from which you can
select. See Chapter 7.9.5.4 Multimonitoring items
(P6.5.4).
* If the AC drive only has +24V supply (for control board power-up), this value is not reliable.
See All-in-One Application Manual for more monitoring values.