20 • vacon
ELECTRICAL CONNECTION
Tel: +358-201-2121 • Fax: +358-201-212 205
PE busbar
L1 L2 L3
DC-
DC+
Opening for
cables
Figure 5-7. Inverter connection to solar panels, NXV0040 to NXV0100
Model
Minimum cross section
Recommended cross section
Maximum cross section
NXV0010
2x6mm
2
2x50mm
2
2x 2x95mm
2
NXV0015
2x16mm
2
2x70mm
2
2x 2x95mm
2
NXV0020
2x25mm
2
2x95mm
2
2x 2x95mm
2
NXV0025
2x35mm
2
2x95mm
2
2x 2x95mm
2
NXV0030
2x35mm
2
2x 2x70mm
2
2x 2x95mm
2
NXV0040
2x70mm
2
2x 2x95mm
2
4x 2x185mm
2
NXV0050
2x95mm
2
2x 2x95mm
2
4x 2x185mm
2
NXV0080
2x 2x70mm
2
4x 2x95mm
2
4x 2x185mm
2
NXV0100
2x 2x95mm
2
4x 2x95mm
2
4x 2x185mm
2
Table 5-3. Panel input cable dimensions
Model
Minimum cross section
Recommended cross section
Maximum cross section
NXV0010
3x1,5mm
2
3x16mm
2
3x50mm
2
NXV0015
3x1,5mm
2
3x25mm
2
3x50mm
2
NXV0020
3x1,5mm
2
3x25mm
2
3x50mm
2
NXV0025
3x1,5mm
2
3x35mm
2
3x50mm
2
NXV0030
3x1,5mm
2
3x50mm
2
3x50mm
2
NXV0040
3x16mm
2
3x50mm
2
3x120mm
2
NXV0050
3x25mm
2
3x70mm
2
3x120mm
2
NXV0080
3x50mm
2
3x95mm
2
3x120mm
2
NXV0100
3x70mm
2
3x120mm
2
3x120mm
2
Table 5-4. Panel output cable dimensions