28 • vacon
ELECTRICAL CONNECTION
Tel: +358-201-2121 • Fax: +358-201-212 205
5.3.1
Option board OPTB5
Description:
I/O expander board with three relay outputs.
Allowed slots:
B, C, D, E
Type ID:
16949
Terminals:
Three terminal blocks; Screw terminals (M3); No coding
Jumpers:
None
Board parameters:
None
I/O terminals on OPTB5
Terminal
Parameter reference
Keypad/NCDrive
Technical information
22
23
RO1/common
RO1/normal open
DigOUT:X.1
Switching capacity
24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load
5V/10mA
25
26
RO2/common
RO2/normal open
DigOUT:X.2
Switching capacity
24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load
5V/10mA
28
29
RO3/common
RO3/normal open
DigOUT:X.3
Switching capacity
24VDC/8A
250VAC/8A
125VDC/0.4A
Min. switching load
5V/10mA
Table 5-9. OPTB5 I/O terminals
Note: This expander board can be placed into four different slots on the control board. Therefore,
the 'X' given in the Parameter reference shall be replaced by the slot letter (B, C, D, or E) depending
on the slot which the expander board is plugged into.
Summary of Contents for NXV0010