background image

START UP 

vacon • 37 

24-hour  support:  +358 (0)201 212 575 •  Email:  vacon@vacon.com 

 

6.1.5.1

 

Monitoring menu 

To enter the Monitoring menu from the Main menu, press the Push button Menu right when the lo-

cation indication M1 appears in the first line of the screen. The following figure shows how to view 

the monitored values. 

The monitored signals have the indication V#.# and are listed in the following table. Values are up-

dated every 0.3 seconds. 

 

This menu is used only to verify the signals. Values can not be modified. 

 

 

 

 
 

 

 
 

Code 

Parameter 

Min 

Max 

Unit 

ID 

Description 

V1.1 

Output power 

1000 

kW 

1707 

Output power of inverter, with compensated 
LCL filter losses. 

V1.2 

Total energy kWh 

4,29E+09 

kWh 

1837 

Total energy of inverter fed into the grid. 

V1.3 

Energy today kWh 

6553,5 

kWh 

1708 

Energy fed into the grid today. 

V1.4 

Energy yesterday 

6553,5 

kWh 

1733 

Energy fed into the grid yesterday. 

V1.5 

DC voltage refer-

ence 

50 

150 

1200 

Used DC voltage reference by the regenerative 
unit in % of the nominal DC voltage. 

V1.6 

DC-link voltage 

1000 

1839 

Filtered DC-link voltage in Volt. 

V1.7 

Unit temperature 

-50 

200 

°C 

1109 

Temperature of the unit in Celsius 

V1.8 

AC voltage 

1000 

1709 

AC voltage measured on the grid side of the 
main contactor by an external measurement 
circuit. 

V1.9 

AC frequency 

-60 

60 

Hz 

1835 

Grid frequency in Hz. The sign indicates the 
phase order. Can be monitored only when 
UNIT is in RUN state. 

V1.10 

Output current 

Varies 

1834 

Output current of the inverter coming out of 
the cabinet (transformers inside cabinet are 

taken into consideration). 

V1.11 

Run time total [h] 

99999999 

1836 

Total time the inverter has been running. 

V1.12 

Run time today 

255 

1731 

The time the inverter has been running today. 

V1.13 

Run time yesterday 

255 

1732 

The time the inverter ran yesterday. 

V1.14 

Grid connections 

4,29E+09 

 

1706 

Total number of times the inverter has closed 

the main contactor and connected to the grid. 

V1.15 

Standby remaining 

65535 

1201 

Remaining time in standby mode, if standby 

mode is activated. 

Table 6-1. Monitoring values

 

 

RUN

READY

Local

M1

Monitor

V1

V14

RUN

READY

Local

V1.1

Output power

19.4 kW

RUN

READY

Local

V1.1

Daily energy

125 kWh

Summary of Contents for NXV0010

Page 1: ...user s manual 3 phase photovoltaic inverters for connection to mains supply drives nxv0010 to nxv0100...

Page 2: ...Y 7 3 1 Type designation code 7 3 2 Lifting the unit out of the transport packaging 7 3 3 Storage 8 3 4 Maintenance 9 3 5 Warranty 9 4 INSTALLATION 10 4 1 Free space around the cabinet 12 4 2 Fixing t...

Page 3: ...WED TO CARRY OUT THE ELECTRICAL IN STALLATION RISK OF ELECTRIC SHOCK The solar inverter VACON 8000 SOLAR has been designed to be installed in enclosed places It shall be protected against harsh weathe...

Page 4: ...e equipment PPEs must be used Helmet Safety goggles for electrical risk Safety footwear Electrically resistant gloves adequate for the voltage Protective gloves against mechanical risk Access to the p...

Page 5: ...not form a part of the supply cable or cable enclosure shall in any case be not less than 2 5 mm2 if mechanical protection is provided or 4 mm2 if mechanical protection is not provided For cord connec...

Page 6: ...Hz 0 5 Cos 0 99 for output 20 100 of Pn Harmonic distortion 2 5 for output 30 of power Consumption at night 5W NXV0010 NXV0030 30 W NXV0040 NXV0100 Maximum efficiency 94 96 Ambient temperature 10 40 C...

Page 7: ...environment and rated voltage less than 1000V T fulfils standard EN61800 3 2004 when used in IT networks Option boards each slot is represented by two characters where A basic I O board B expander I...

Page 8: ...o be kept in store before use make sure that the ambient conditions are acceptable Storing temperature 40 70 C Relative humidity 95 no condensation The environment should also be free from dust If the...

Page 9: ...cor rosion on terminals busbars and other surfaces 5 7 years Change cooling fans main fan fan of the LCL filter 5 10 years Change DC bus capacitors if DC voltage ripple is high Table 3 1 Proactive ma...

Page 10: ...on instructions included in this manual The IP21 protection of the VACON 8000 SOLAR inverter only allows for installation in enclosed places Note the locations of some essential components of the inve...

Page 11: ...e The equipment has to be installed in a place where the room temperature is between 10 C and 40 C Lower temperatures prevent the equipment from starting up and higher temperatures limit the output po...

Page 12: ...g air required is indicated in the table below Also make sure that the tempera ture of the cooling air does not exceed the maximum ambient temperature of the inverter 200 mm 800 mm 25 mm Figure 4 3 Sp...

Page 13: ...net can be fixed to the floor alone or to the floor and the back wall 4 2 1 Fixing the unit to floor alone For the floor only mounting the fixing points in all four bottom corners of the cabinet shown...

Page 14: ...p Flip it and refix the screws as shown in Figure 4 5 2 Then bolt the cabinet to the floor at the fixing points on the bottom front side see Figure 4 5 BOTTOM VIEW FRONT REAR Rear iron clamp Figure 4...

Page 15: ...hich may cause death or serious injury 5 1 Electrical diagrams 5 1 1 NXV0010 to NXV0030 R BE1 RF5 340 800VDC 30A 3Ph 400V 50Hz 22A QA1 4 TB2 3 2 3 RA1 3 CA1 QA5 QA2 3 FC4 3 FA1 3 PE1 FCP 2 TA0 3 PE 3...

Page 16: ...1 2121 Fax 358 201 212 205 5 1 3 NXV0080 to NXV0100 R BE1 RF5 340 800VDC 200A 3Ph 400V 50Hz 145A TB2 3 2 3 RA1 1 3 CA1 QA5 FC4 3 FA1 3 PE1 FCP 2 TA0 3 PE 3 PE1 01 QB1 FC3 2 RA1 2 3 QA2 3 I Figure 5 3...

Page 17: ...o which all the inverter s metallic parts are connected This connection terminal must be connected to earth Remember to earth the PE busbar See Table 5 1 on page 18 5 2 2 Connection to mains The termi...

Page 18: ...mm2 AC DC PE AC DC PE NXV0010 1 5 6 10 50 95 240 NXV0015 1 5 6 10 50 95 240 NXV0020 1 5 6 10 50 95 240 NXV0025 1 5 6 10 50 95 240 NXV0030 1 5 6 10 50 95 240 NXV0040 10 10 10 240 240 240 NXV0050 10 10...

Page 19: ...respective terminals on the drive through the bottom of the supply unit see Figure 5 5 and Figure 5 6 Check for the cable sizes and the appropriate number of cables in tables on page 20 In drives NXV...

Page 20: ...2x95mm2 NXV0040 2x70mm2 2x 2x95mm2 4x 2x185mm2 NXV0050 2x95mm2 2x 2x95mm2 4x 2x185mm2 NXV0080 2x 2x70mm2 4x 2x95mm2 4x 2x185mm2 NXV0100 2x 2x95mm2 4x 2x95mm2 4x 2x185mm2 Table 5 3 Panel input cable di...

Page 21: ...XV0020 16mm2 NXV0025 16mm2 NXV0030 16mm2 NXV0040 25mm2 NXV0050 25mm2 NXV0080 35mm2 NXV0100 35mm2 Table 5 5 Panel earthing cable dimensions The minimum cable cross section is calculated in compliance w...

Page 22: ...de the control unit of the Vacon 8000 Solar inverter see Figure 5 8 Four different board types can be used with the inverter A1 A2 B5 C2 and D7 The control connections of these boards are described be...

Page 23: ...T A1 option board Description Standard I O board with digital inputs outputs and analogue inputs outputs Allowed slots A Type ID 16689 Terminals Two terminal blocks coded mounting of blocks in wrong o...

Page 24: ...nically connected to terminal 12 7 GND Ground for reference and controls Galvanically connected to terminals 13 19 8 DIN1 DigIN A 1 Digital input 1 Common CMA Ri min 5k 9 DIN2 DigIN A 2 Digital input...

Page 25: ...de AI1 mode Voltage input 0 10V AI1 mode Voltage input 0 10V differential AI1 mode Voltage input 10 10V Jum per block X2 AI2 m ode AI2 mode 0 20mA Current input AI2 mode Voltage input 0 10V AI2 mode V...

Page 26: ...OPTA1 parameters Number Parameter Min Max Default Note 1 AI1 mode 1 5 3 1 0 20mA 2 4 20mA 3 0 10V 4 2 10V 5 10 10V 2 AI2 mode 1 5 1 1 0 20mA 2 4 20mA 3 0 10V 4 2 10V 5 10 10V 3 AO1 mode 1 4 1 1 0 20m...

Page 27: ...Jumpers None Board parameters None I O terminals on OPTA2 Terminal Parameter reference on keypad and NCDrive Technical information 21 22 23 RO1 normal closed RO1 common RO1 normal open DigOUT B 1 Rela...

Page 28: ...igOUT X 1 Switching capacity 24VDC 8A 250VAC 8A 125VDC 0 4A Min switching load 5V 10mA 25 26 RO2 common RO2 normal open DigOUT X 2 Switching capacity 24VDC 8A 250VAC 8A 125VDC 0 4A Min switching load...

Page 29: ...nector Description NC 1 No connection VP 2 Supply voltage plus 5V RxD TxD N 3 Receive Transmit data A RxD TxD P 4 Receive Transmit data B DGND 5 Data ground reference potential for VP You can use this...

Page 30: ...mming tool The OPTD7 board is delivered with the transformer which is suitable for voltage range 380V 690V Please note that the transformer can not be used with the pulse width modulated PWM voltage i...

Page 31: ...ransformer ratio Primary secondary 60 1 Transformer second ary output voltage range 14V rms Between the terminals L1 L2 L3 Input impedence L1 L2 50kOhm L1 L3 25kOhm L2 L3 25kOhm L3 is internal virtual...

Page 32: ...rrent A Nominal voltage V Braking capacity kA Acting behaviour Fuse size Suitable fuse type Cat nr by Ferraz Shawmut NXV0010 No fuses needed NXV0015 NXV0020 NXV0025 NXV0030 NXV0040 160 1200 100 gPV 12...

Page 33: ...y including the earth cable are correct ly connected Check that the main AC circuit breaker and possible auxiliary circuit breakers are connected and closed 3 Press the START button on the control pan...

Page 34: ...fault RUN The inverter is running Indicates the order of phases in the mains STOP Indicates that the inverter is not running READY Illuminated when DC level is OK In case of a fault the symbol will no...

Page 35: ...shows a description of the fault see chapter Active Faults 6 1 3 Text lines The three text lines provide the user with information about the current location within the menu structure of the panel sep...

Page 36: ...top the inverter 6 1 5 Browsing the control panel Data on the control panel is arranged in menus and submenus Menus are used for example to dis play control signals and the measurements of reference v...

Page 37: ...nal DC voltage V1 6 DC link voltage 0 1000 V 1839 Filtered DC link voltage in Volt V1 7 Unit temperature 50 200 C 1109 Temperature of the unit in Celsius V1 8 AC voltage 0 1000 V 1709 AC voltage measu...

Page 38: ...here you were before the fault trip The fault is active until it is deleted with the Reset push button Normal state no faults 6 1 5 3 Fault history menu M5 The Fault history menu can be accessed from...

Page 39: ...at least once a year Visually check the external condition of the inverter checking mainly the good condition of the door and its locking elements Visually check the internal condition of the inverter...

Page 40: ...how to solve them THE SOLUTION FOR SOME OF THE PROBLEMS INDICATED HERE IMPLIES TO PER FORM CHECKING INSIDE THE INVERTER THE WIRES OF AC MAINS OR THE DC WIRES IN THE SOLAR PANELS THESE CHECKS HAVE TO B...

Page 41: ...11 Input phase supervision Input line phase is missing Check supply voltage fuses and cable 13 Frequency con verter under temperature Heatsink temperature is under 10 C 14 Frequency con verter over t...

Page 42: ...or near to you Please visit http www vacon com wwcontacts html 41 IGBT tempera ture IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current Check loading 44...

Page 43: ...limit Check AC Voltage 74 FreqOverLimit AC frequency on line side is above the max limit Check AC Frequency 75 FreqUnderLimit AC frequency on line side is below the min limit Check AC Frequency 76 DC...

Page 44: ...Vacon distributor...

Reviews: